OpINNonDir> = On
&
OpUN> = On
&
t
tUN
OpMode = 3I0Cosfi
&
OpMode = 3I0 and fi
&
OpMode = 3I03U0Cosfi
&
RCADir
RCAComp
ROADir
&
DirMode = Forward
DirMode = Reverse
³
1
&
&
&
³
1
t
tDef
t
tDef
³
1
STDIRIN
TRDIRIN
STNDIN
TRNDIN
STUN
TRUN
STFW
STRV
t
S
N
TimeChar
INNonDir>
&
Direction
Detection
Logic
t
IN
UN>
INCosPhi>
INDir>
SN>
INRel>
UNRel>
IEC06000653.vsd
IEC06000653 V4 EN
Figure 181:
Simplified logical diagram of the sensitive earth fault current protection
8.6.8
Technical data
Table 193:
SDEPSDE technical data
Function
Range or value
Accuracy
Operate level for 3I
0
·cos
j
directional residual
overcurrent
(0.25-200.00)% of
lBase
± 1.0% of I
r
at I
£
I
r
± 1.0% of I at I > I
r
Operate level for ·3I
0
·3U
0
cos
j
directional residual power
(0.25-200.00)% of
SBase
± 1.0% of S
r
at S
£
S
r
± 1.0% of S at S > S
r
Operate level for 3I
0
and
j
residual overcurrent
(0.25-200.00)% of
lBase
± 1.0% of I
r
at
£
I
r
± 1.0% of I at I > I
r
Table continues on next page
1MRK502052-UEN B
Section 8
Current protection
399
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...