Screw
terminal
X3
1
2
1
2
3
4
5
6
Screw
terminal
X1
Backplane
Angle
bracket
RS485
PWB
IEC06000517 V1 EN
Figure 538:
RS485 connector
•
2-wire: Connect pin 1 to pin 6 and pin 2 to pin 5
•
Termination (2-wire): Connect pin 1 to pin 3
•
Termination (4-wire): Connect pin 1 to pin 3 and pin 4 to pin 6
Soft ground connector pinouts
A second 2-pole screw connector is used for the connection of IO-ground. It can be
used in two combinations like:
•
Unconnected: No ground of the IO-part · .
•
Soft grounded: The IO is connected to the GND with an RC net parallel with a
MOV
21.2.13.3
Technical data
Table 921:
Galvanic RS485 communication module
Quantity
Range or value
Communication speed
2400–19200 bauds
External connectors
RS-485 6-pole connector
Soft ground 2-pole connector
Section 21
1MRK502052-UEN B
IED hardware
1188
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...