Quantity
Rated value
Nominal range
Counter input frequency
10 pulses/s max
-
Oscillating signal discriminator
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Debounce filter
Settable 1–20 ms
Maximum 176 binary input channels may be activated
simultaneously with influencing factors within nominal range.
Table 894:
BIM - Binary input module with enhanced pulse counting capabilities
Quantity
Rated value
Nominal range
Binary inputs
16
-
DC voltage, RL
24/30 V
48/60 V
110/125 V
220/250 V
RL
±
20%
RL
±
20%
RL
±
20%
RL
±
20%
Power consumption
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
-
Counter input frequency
10 pulses/s max
-
Balanced counter input frequency
40 pulses/s max
-
Oscillating signal discriminator
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Debounce filter
Settable 1-20 ms
Maximum 176 binary input channels may be activated
simultaneously with influencing factors within nominal range.
21.2.8
Binary output modules (BOM)
21.2.8.1
Introduction
The binary output module has 24 independent output relays and is used for trip output
or any signaling purpose.
21.2.8.2
Design
The binary output module (BOM) has 24 software supervised output relays. Each pair
of relays have a common power source input to the contacts, see figure
should be considered when connecting the wiring to the connection terminal on the
back of the IED.
1MRK502052-UEN B
Section 21
IED hardware
1161
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...