background image

Table 72. Third harmonic-based stator earth-fault protection (H3EFPSEF) main settings

Parameter

Function

Value (Range)

Step

Beta

H3EFPSEF

0.50...10.00

0.01

Voltage N 3.H Lim

H3EFPSEF

0.005...0.200 × U

n

0.001

Operate delay time

H3EFPSEF

20...300000 ms

10

Voltage selection

H3EFPSEF

1 = No voltage
2 = Measured Uo
3 = Calculated Uo
4 = Phase A
5 = Phase B
6 = Phase C

-

CB open factor

H3EFPSEF

1.00...10.00

0.01

Table 73. Underpower protection (DUPPDPR)

Characteristic

Value

Operation accuracy 

1)

Depending on the frequency of the measured current and voltage:
f

n

 ±2 Hz

Power measurement accuracy ±3% of the set value or ±0.002 × S

n

Phase angle: ±2°

Start time

2)3)

Typically 45 ms

Reset time

Typically 30 ms

Reset ratio

Typically 1.04

Operate time accuracy

±1.0% of the set value of ±20 ms

Suppression of harmonics

-50 dB at f = n × f

n

, where n = 2, 3, 4, 5,…

1)

Measurement mode = “Pos Seq” (default)

2)

U = U

n

, f

n

 = 50 Hz, results based on statistical distribution of 1000 measurements

3)

Includes the delay of the signal output contact

Table 74. Underpower protection (DUPPDPR) main settings

Parameter

Function

Value (Range)

Step

Start value

DUPPDPR

0.01...2.00 × S

n

0.01

Operate delay time

DUPPDPR

40...300000 ms

10

Pol reversal

DUPPDPR

0 = False
1 = True

-

Disable time

DUPPDPR

0...60000 ms

1000

Generator and Interconnection Protection

1MRS758279 B

REG615

 

Product version: 5.0 FP1

 
 

48

ABB

Summary of Contents for RELION REG615

Page 1: ...Relion 615 series Generator and Interconnection Protection REG615 Product Guide ...

Page 2: ... data 62 24 Accessories and ordering data 63 25 Tools 64 26 Cyber security 65 27 Terminal diagrams 66 28 Certificates 69 29 References 69 30 Functions codes and symbols 70 31 Document revision history 74 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB ABB assumes no responsibility for any errors that may appear in t...

Page 3: ...nt protection system is required The interconnection protection relay provides main protection fulfilling the grid codes to connect distributed generation with the power grid The 615 series relays support a range of communication protocols including IEC 61850 with Edition 2 support process bus according to IEC 61850 9 2 LE IEC 60870 5 103 Modbus and DNP3 Profibus DPV1 communication protocol is sup...

Page 4: ...otocols IEC 61850 8 1 9 2LE Modbus IEC 60870 5 103 DNP3 Interfaces Ethernet TX RJ45 FX LC Serial Serial glass fiber ST RS 485 RS 232 Redundant protocols HSR PRP RSTP CONDITION MONITORING AND SUPERVISION OR AND 2 Object Ctrl 2 Ind 3 CB DC ES 1 Check availability of binary inputs outputs from technical documentation Control and indication function for primary object Status indication function for pri...

Page 5: ...trical components Frequency adaptivity 4 5 Analog interface types 1 Current transformer Voltage transformer 1 Conventional transformer inputs PQM3U PQM3V PQMU PQMV PQM3I PQM3I 2 RTD 1 mA MAP MAP 18 OR AND dUo Uo3H 27 59THD Master Trip Lockout relay 94 86 U2 47O U1 47U 3U 27 2 2 2 3U 59 f f df dt 81 2 6 U f 24 3I ARC 50L 50NL 3I 50P 51P 3I2f 68 3I Io BF 51BF 51NBF P Q 32R 32O 3 3I 51P 1 3I 51P 2 I2...

Page 6: ...ION COMMUNICATION Protocols IEC 61850 8 1 9 2LE Modbus IEC 60870 5 103 DNP3 Interfaces Ethernet TX RJ45 FX LC Serial Serial glass fiber ST RS 485 RS 232 Redundant protocols HSR PRP RSTP 3I 3I UL1 L2 L3 Io Master Trip Lockout relay 94 86 Io 67N 1 Io 67N 2 2 U12 Uo MEASUREMENT I U Io Uo P Q E pf f Limit value supervision Load profile record RTD mA measurement optional Symmetrical components Frequency ...

Page 7: ...TR 1 Three phase thermal overload protection two time constants T2PTTR 1 1 Circuit breaker failure protection CCBRBRF 1 1 2 1 2 Three phase inrush detector INRPHAR 1 1 1 Master trip TRPPTRC 2 3 3 3 3 3 3 3 3 Arc protection ARCSARC 3 3 2 3 2 Multipurpose protection MAPGAPC 18 18 18 Stabilized and instantaneous differential protection for machines MPDIF 1 Third harmonic based stator earth fault prot...

Page 8: ...on TPMGAPC 1 1 1 Pulse timer 8 pcs PTGAPC 2 2 2 Time delay off 8 pcs TOFGAPC 4 4 4 Time delay on 8 pcs TONGAPC 4 4 4 Set reset 8 pcs SRGAPC 4 4 4 Move 8 pcs MVGAPC 2 2 2 Generic control point 16 pcs SPCGAPC 2 2 2 Analog value scaling 4 pcs SCA4GAPC 4 4 4 Integer value move 4 pcs MVI4GAPC 1 1 1 1 2 Number of included instances The instances of a protection function represent the number of identical...

Page 9: ...relay can be used to support utility grid stability and to detect islanding The protection allows the monitoring of distributed generation during low voltage or fault ride through to determine whether and when to disconnect from the grid The voltage vector shift protection detects islanding from the grid by measuring continuously the duration of the voltage cycle and it can be further secured with...

Page 10: ...r plant as distributed power generation coupled into the utility network Standard configuration A is not designed for using all the available functionality content in one relay at the same time Directional earth fault protection functions must be added with the Application Configuration tool In order to ensure the performance of the relay the user specific configuration load is verified with the A...

Page 11: ... generator field excitation system and primary mover A typical application example is parallel connected diesel or gas generators with a common step up transformer but it can also be a generator in block connection with a transformer In medium size power generator applications independent and redundant protection system can be a requirement or the protection system as a whole may require more than...

Page 12: ...3I 3I 3I U Uo FUSEF Io Io f f df dt C 3U 3I Io G Uo Io 3U 3I Io G Uo Io GUID FA8F2E27 11C7 4B88 8865 414DFB0D71F3 V1 EN Figure 6 Application example for parallel with common step up transformer connected Diesel Gas generators protected with standard configuration C Figure 6 illustrates several generator units connected in parallel Each unit is individually high resistance earthed Earth fault curre...

Page 13: ...emented with two REG615 generator protection relays One REG615 takes care of the generator protection with 100 stator earth fault protection and the other REG615 provides the generator differential protection Standard configuration D is not designed for using all the available functionality content in one relay at the same time Three phase directional overcurrent protection three phase voltage pro...

Page 14: ... with a transformer protection application example with standard configuration C and RET615 In Figure 8 generator protection is implemented with REG615 generator protection relay Transformer protection is implemented with the RET615 transformer differential protection relay covering the generator in block connection with a transformer A single phase voltage transformer is connected to the generato...

Page 15: ...M600S features a Web browser based HMI which provides a customizable graphical display for visualizing single line mimic diagrams for switchgear bay solutions The SLD feature is especially useful when 615 series relays without the optional single line diagram feature are used The Web HMI of COM600S also provides an overview of the whole substation including relay specific single line diagrams whic...

Page 16: ...ending on the chosen standard configuration of the relay the number of unused binary inputs and binary outputs varies Further some standard configurations also offer optional hardware modules that increase the number of available binary inputs and outputs If the amount of available binary inputs or outputs of the chosen standard configuration is not sufficient the standard configuration can be mod...

Page 17: ...system In fact the majority of power quality problems are localized within customer facilities Thus power quality monitoring is not only an effective customer service strategy but also a way to protect a utility s reputation for quality power and service The protection relay has the following power quality monitoring functions Voltage variation Voltage unbalance Current harmonics Voltage harmonics...

Page 18: ...time interval Demand interval 1 180min Function specific data Min max demand currents Operation counters etc History view GUID CDF1DC16 AF90 406F B21B EF6C7F60BCCA V1 EN Figure 10 Recording and event capabilities overview 12 Condition monitoring The condition monitoring functions of the relay constantly monitor the performance and the condition of the circuit breaker The monitoring comprises the s...

Page 19: ...tage inputs and one residual voltage input and one voltage input that is used either for synchro check or for the 3rd harmonic based stator earth fault protection depending on the standard configuration The phase current inputs are rated 1 5 A Two optional residual current inputs are available that is 1 5 A or 0 2 1 A The 0 2 1 A input is normally used in applications requiring sensitive earth fau...

Page 20: ...pports monitoring and control functions Additionally parameter settings disturbance recordings and fault records can be accessed using the IEC 61850 protocol Disturbance recordings are available to any Ethernet based application in the standard COMTRADE file format The relay supports simultaneous event reporting to five different clients on the station bus The relay can exchange data with other de...

Page 21: ...the duplication of all transmitted information and provide a zero switch over time if the links or switches fail thus fulfilling all the stringent real time requirements of substation automation In PRP each network node is attached to two independent networks operated in parallel The networks are completely separated to ensure failure independence and can have different topologies The networks ope...

Page 22: ...with standard Rapid Spanning Tree Protocol RSTP support The managed switch controls the consistency of the loop routes the data and corrects the data flow in case of a communication switch over The relays in the ring topology act as unmanaged switches forwarding unrelated data traffic The Ethernet ring solution supports the connection of up to 30 615 series relays If more than 30 relays are to be ...

Page 23: ...rent masters Besides basic standard functionality the relay supports changing of the active setting group and uploading of disturbance recordings in IEC 60870 5 103 format Further IEC 60870 5 103 can be used at the same time with the IEC 61850 protocol DNP3 supports both serial and TCP modes for connection up to five masters Changing of the active setting and reading fault records are supported DN...

Page 24: ...ation Required accuracy of grandmaster clock is 1 µs The relay can work as a master clock per BMC algorithm if the external grandmaster clock is not available for short term The IEEE 1588 support is included in all variants having a redundant Ethernet communication module In addition the relay supports time synchronization via Modbus DNP3 and IEC 60870 5 103 serial communication protocols Table 5 ...

Page 25: ...ary voltage supply under quiescent Pq operating condition DC 13 0 W nominal 18 0 W max AC 16 0 W nominal 21 0 W max DC 13 0 W nominal 18 0 W max Ripple in the DC auxiliary voltage Max 15 of the DC value at frequency of 100 Hz Fuse type T4A 250 V Table 8 Energizing inputs Description Value Rated frequency 50 60 Hz Current inputs Rated current In 0 2 1 A1 1 5 A2 Thermal withstand capability Continuo...

Page 26: ...esistance three wire measurement 25 Ω per lead Isolation 2 kV inputs to protective earth Response time 4 s RTD resistance sensing current Maximum 0 33 mA rms Operation accuracy Resistance Temperature 2 0 or 1 Ω 1 C 10 Ω copper 2 C mA inputs Supported current range 0 20 mA Current input impedance 44 Ω 0 1 Operation accuracy 0 5 or 0 01 mA Table 11 Signal output X100 SO1 Description Value Rated volt...

Page 27: ...he control circuit time constant L R 40 ms at 48 110 220 V DC two contacts connected in series 5 A 3 A 1 A Minimum contact load 100 mA at 24 V AC DC Trip circuit supervision TCS Control voltage range 20 250 V AC DC Current drain through the supervision circuit 1 5 mA Minimum voltage over the TCS contact 20 V AC DC 15 20 V Table 14 Single pole power output relays Description Value Rated voltage 250...

Page 28: ...ted Logic level 5 V TTL Current consumption 4 mA Power consumption 20 mW 1 According to the 200 04 IRIG standard Table 18 Degree of protection of flush mounted protection relay Description Value Front side IP 54 Rear side connection terminals IP 20 Table 19 Environmental conditions Description Value Operating temperature range 25 55ºC continuous Short time service temperature range 40 85ºC 16h 1 2...

Page 29: ...60255 26 class III 10 V m f 900 MHz ENV 50204 IEC 60255 26 class III 20 V m rms f 80 1000 MHz IEEE C37 90 2 2004 Fast transient disturbance test IEC 61000 4 4 IEC 60255 26 IEEE C37 90 1 2002 All ports 4 kV Surge immunity test IEC 61000 4 5 IEC 60255 26 Communication 1 kV line to earth Other ports 4 kV line to earth 2 kV line to line Power frequency 50 Hz magnetic field immunity test IEC 61000 4 8 ...

Page 30: ...µV m peak 56 dB µV m average measured at 3 m distance 3 6 GHz 80 dB µV m peak 60 dB µV m average measured at 3 m distance Table 21 Insulation tests Description Type test value Reference Dielectric tests 2 kV 50 Hz 1 min 500 V 50 Hz 1 min communication IEC 60255 27 Impulse voltage test 5 kV 1 2 50 μs 0 5 J 1 kV 1 2 50 μs 0 5 J communication IEC 60255 27 Insulation resistance measurements 100 MΩ 500...

Page 31: ... 3 h at 25 C 55 C IEC60068 2 14 Storage test 96 h at 40ºC 96 h at 85ºC IEC 60068 2 1 IEC 60068 2 2 Table 24 Product safety Description Reference LV directive 2006 95 EC Standard EN 60255 27 2013 EN 60255 1 2009 Table 25 EMC compliance Description Reference EMC directive 2004 108 EC Standard EN 60255 26 2013 Table 26 RoHS compliance Description Complies with RoHS directive 2002 95 EC Generator and ...

Page 32: ...o P backup No suppression 1 Set Operate delay time 0 02 s Operate curve type IEC definite time Measurement mode default depends on stage current before fault 0 0 In fn 50 Hz fault current in one phase with nominal frequency injected from random phase angle results based on statistical distribution of 1000 measurements 2 Includes the delay of the signal output contact 3 Includes the delay of the he...

Page 33: ...nt mode and Pol quantity default current before fault 0 0 In voltage before fault 1 0 Un fn 50 Hz fault current in one phase with nominal frequency injected from random phase angle results based on statistical distribution of 1000 measurements 2 Includes the delay of the signal output contact 3 Maximum Start value 2 5 In Start value multiples in range of 1 5 20 Table 30 Three phase directional ove...

Page 34: ...se with nominal frequency injected from random phase angle results based on statistical distribution of 1000 measurements 2 Includes the delay of the signal output contact Table 32 Three phase voltage dependent overcurrent protection PHPVOC main settings Parameter Function Value Range Step Start value PHPVOC 0 05 5 00 In 0 01 Start value low PHPVOC 0 05 1 00 In 0 01 Voltage high limit PHPVOC 0 01 ...

Page 35: ... Peak to Peak No suppression 1 Measurement mode default depends on stage current before fault 0 0 In fn 50 Hz earth fault current with nominal frequency injected from random phase angle results based on statistical distribution of 1000 measurements 2 Includes the delay of the signal output contact 3 Maximum Start value 2 5 In Start value multiples in range of 1 5 20 Table 34 Non directional earth ...

Page 36: ...y 40 ms Reset ratio Typically 0 96 Retardation time 30 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 20 ms 3 Suppression of harmonics RMS No suppression DFT 50 dB at f n fn where n 2 3 4 5 Peak to Peak No suppression 1 Set Operate delay time 0 06 s Operate curve type IEC definite time Measurem...

Page 37: ...erating characteristics table Table 37 Transient intermittent earth fault protection INTRPTEF Characteristic Value Operation accuracy Uo criteria with transient protection Depending on the frequency of the measured current fn 2 Hz 1 5 of the set value or 0 002 Uo Operate time accuracy 1 0 of the set value or 20 ms Suppression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 Table 38 Transient inte...

Page 38: ...alue NSPTOC 0 01 5 00 In 0 01 Time multiplier NSPTOC 0 05 15 00 0 01 Operate delay time NSPTOC 40 200000 ms 10 Operating curve type1 NSPTOC Definite or inverse time Curve type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 18 19 1 For further reference see the Operation characteristics table Table 41 Negative sequence overcurrent protection for machines MNSPTOC Characteristic Value Operation accuracy Depe...

Page 39: ...Fault 2 set Start value 48 ms 51 ms 54 ms Reset time Typically 40 ms Reset ratio Typically 0 96 Retardation time 35 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Suppression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 1 Residual voltage before fault 0 0 Un fn 50 Hz residual voltage with nominal frequency injected from random phase angle results based on statisti...

Page 40: ... 20 Un 0 01 Time multiplier PHPTUV 0 05 15 00 0 01 Operate delay time PHPTUV 60 300000 ms 10 Operating curve type1 PHPTUV Definite or inverse time Curve type 5 15 21 22 23 1 For further reference see the Operation characteristics table Table 47 Three phase overvoltage protection PHPTOV Characteristic Value Operation accuracy Depending on the frequency of the measured voltage fn 2 Hz 1 5 of the set...

Page 41: ...55 ms 47 ms 58 ms 50 ms Reset time Typically 40 ms Reset ratio Depends on the set Relative hysteresis Retardation time 35 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Suppression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 1 Start value 1 0 Un positive sequence voltage before fault 1 1 Un fn 50 Hz positive sequence undervoltage with nominal frequency injected f...

Page 42: ... Un fn 50 Hz negative sequence overvoltage with nominal frequency injected from random phase angle results based on statistical distribution of 1000 measurements 2 Includes the delay of the signal output contact Table 52 Negative sequence overvoltage protection NSPTOV main settings Parameter Function Value Range Step Start value NSPTOV 0 010 1 000 Un 0 001 Operate delay time NSPTOV 40 120000 ms 1 ...

Page 43: ... Typically 200 ms Voltage change Typically 40 ms Reset time Typically 40 ms Reset ratio Typically 0 96 Retardation time 35 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 50 ms 1 fn 50 Hz results based on statistical distribution of 1000 measurements 2 Includes the delay of the signal output con...

Page 44: ...se temperature T1PTTR 20 0 150 0 C 0 1 Current multiplier T1PTTR 1 5 1 Initial temperature T1PTTR 50 0 100 0 C 0 1 Table 59 Three phase thermal overload protection two time constants T2PTTR Characteristic Value Operation accuracy Depending on the frequency of the measured current fn 2 Hz Current measurement 1 5 of the set value or 0 002 x In at currents in the range of 0 01 4 00 x In Operate time ...

Page 45: ...3 Both CB fail trip mode CCBRBRF 1 Off 2 Without check 3 Current check Retrip time CCBRBRF 0 60000 ms 10 CB failure delay CCBRBRF 0 60000 ms 10 CB fault delay CCBRBRF 0 60000 ms 10 Table 63 Three phase inrush detector INRPHAR Characteristic Value Operation accuracy At the frequency f fn Current measurement 1 5 of the set value or 0 002 In Ratio I2f I1f measurement 5 0 of the set value Reset time 3...

Page 46: ... delay of the heavy duty output contact 3 Normal power output 4 High speed output Table 66 Arc protection ARCSARC main settings Parameter Function Value Range Step Phase start value ARCSARC 0 50 40 00 In 0 01 Ground start value ARCSARC 0 05 8 00 In 0 01 Operation mode ARCSARC 2 Light only 3 BI controlled Table 67 Multipurpose protection MAPGAPC Characteristic Value Operation accuracy 1 0 of the se...

Page 47: ...lue MPDIF 100 1000 Ir 10 Slope section 2 MPDIF 10 50 1 End section 1 MPDIF 0 100 Ir 1 End section 2 MPDIF 100 300 Ir 1 DC restrain enable MPDIF 0 False 1 True CT connection type MPDIF 1 Type 1 2 Type 2 CT ratio Cor Line MPDIF 0 40 4 00 0 01 CT ratio Cor Neut MPDIF 0 40 4 00 0 01 Table 71 Third harmonic based stator earth fault protection H3EFPSEF Characteristic Value Operation accuracy Depending o...

Page 48: ...ent accuracy 3 of the set value or 0 002 Sn Phase angle 2 Start time2 3 Typically 45 ms Reset time Typically 30 ms Reset ratio Typically 1 04 Operate time accuracy 1 0 of the set value of 20 ms Suppression of harmonics 50 dB at f n fn where n 2 3 4 5 1 Measurement mode Pos Seq default 2 U Un fn 50 Hz results based on statistical distribution of 1000 measurements 3 Includes the delay of the signal ...

Page 49: ...eter Function Value Range Step Start value DOPPDPR 0 01 2 00 Sn 0 01 Operate delay time DOPPDPR 40 300000 ms 10 Directional mode DOPPDPR 2 Forward 3 Reverse Power angle DOPPDPR 90 90 1 Table 77 Three phase under excitation protection UEXPDIS Characteristic Value Operation accuracy Depending on the frequency of the measured current and voltage f fn 2 Hz 3 0 of the set value or 0 2 Zb Start time1 2 ...

Page 50: ...s Operate time accuracy 1 0 of the set value or 20 ms 1 fn 50 Hz results based on statistical distribution of 1000 measurements 2 Includes the delay of the signal output contact Table 80 Three phase underimpedance protection UZPDIS main settings Parameter Function Value Range Step Percentage reach UZPDIS 1 6000 Zn 1 Operate delay time UZPDIS 40 200000 ms 10 Table 81 Out of step protection OOSRPSB ...

Page 51: ...one 1 reach OOSRPSB 1 100 1 Table 83 Operation characteristics Parameter Value Range Operating curve type 1 ANSI Ext inv 2 ANSI Very inv 3 ANSI Norm inv 4 ANSI Mod inv 5 ANSI Def Time 6 L T E inv 7 L T V inv 8 L T inv 9 IEC Norm inv 10 IEC Very inv 11 IEC inv 12 IEC Ext inv 13 IEC S T inv 14 IEC L T inv 15 IEC Def Time 17 Programmable 18 RI type 19 RD type Operating curve type voltage protection 5...

Page 52: ... undervoltage protection DQPTUV main settings Parameter Function Value Range Step Voltage start value DQPTUV 0 20 1 20 Un 0 01 Operate delay time DQPTUV 100 300000 ms 10 Min reactive power DQPTUV 0 01 0 50 Sn 0 01 Min Ps Seq current DQPTUV 0 02 0 20 In 0 01 Pwr sector reduction DQPTUV 0 10 1 Table 86 Low voltage ride through protection LVRTPTUV Characteristic Value Operation accuracy Depending on ...

Page 53: ...RTPTUV 0 00 1 20 ms 0 01 Voltage level 9 LVRTPTUV 0 00 1 20 ms 0 01 Voltage level 10 LVRTPTUV 0 00 1 20 ms 0 01 Recovery time 1 LVRTPTUV 0 300000 ms 1 Recovery time 2 LVRTPTUV 0 300000 ms 1 Recovery time 3 LVRTPTUV 0 300000 ms 1 Recovery time 4 LVRTPTUV 0 300000 ms 1 Recovery time 5 LVRTPTUV 0 300000 ms 1 Recovery time 6 LVRTPTUV 0 300000 ms 1 Recovery time 7 LVRTPTUV 0 300000 ms 1 Recovery time 8...

Page 54: ...alue Range Step Start value VVSPPAM 2 0 30 0 0 1 Over Volt Blk value VVSPPAM 0 40 1 50 Un 0 01 Under Volt Blk value VVSPPAM 0 15 1 00 Un 0 01 Phase supervision VVSPPAM 7 Ph A B C 8 Pos sequence Generator and Interconnection Protection 1MRS758279 B REG615 Product version 5 0 FP1 54 ABB ...

Page 55: ...value or 0 2 of reference voltage Reset ratio Typically 0 96 Swell 1 04 Dip Interruption Table 91 Voltage unbalance VSQVUB Characteristic Value Operation accuracy 1 5 of the set value or 0 002 Un Reset ratio Typically 0 96 Generator and Interconnection Protection 1MRS758279 B REG615 Product version 5 0 FP1 ABB 55 ...

Page 56: ...ad Bus L Any 5 Dead L Bus Any 6 One Live Dead 7 Not Both Live Difference voltage SECRSYN 0 01 0 50 Un 0 01 Difference frequency SECRSYN 0 001 0 100 fn 0 001 Difference angle SECRSYN 5 90 1 Synchrocheck mode SECRSYN 1 Off 2 Synchronous 3 Asynchronous Dead line value SECRSYN 0 1 0 8 Un 0 1 Live line value SECRSYN 0 2 1 0 Un 0 1 Max energizing V SECRSYN 0 50 1 15 Un 0 01 Control mode SECRSYN 1 Contin...

Page 57: ...x operate current CCSPVC 1 00 5 00 In 0 01 Table 97 Fuse failure supervision SEQSPVC Characteristic Value Operate time1 NPS function UFault 1 1 set Neg Seq voltage Lev 33 ms UFault 5 0 set Neg Seq voltage Lev 18 ms Delta function ΔU 1 1 set Voltage change rate 30 ms ΔU 2 0 set Voltage change rate 24 ms 1 Includes the delay of the signal output contact fn 50 Hz fault voltage with nominal frequency ...

Page 58: ...alue Operation accuracy Depending on the frequency of the current measured f fn 2 Hz 0 5 or 0 002 In at currents in the range of 0 01 4 00 In Suppression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 RMS No suppression Table 102 Three phase voltage measurement VMMXU Characteristic Value Operation accuracy Depending on the frequency of the voltage measured fn 2 Hz At voltages in range 0 01 1 15 ...

Page 59: ...0 5 2 PF 0 86 which equals sinφ 0 5 Table 106 RTD mA measurement XRGGIO130 Description Value RTD inputs Supported RTD sensors 100 Ω platinum 250 Ω platinum 100 Ω nickel 120 Ω nickel 250 Ω nickel 10 Ω copper TCR 0 00385 DIN 43760 TCR 0 00385 TCR 0 00618 DIN 43760 TCR 0 00618 TCR 0 00618 TCR 0 00427 Supported resistance range 0 2 kΩ Maximum lead resistance three wire measurement 25 Ω per lead Isolat...

Page 60: ...ms Table 109 Time delay off 8 pcs TOFPAGC Characteristic Value Operate time accuracy 1 0 of the set value or 20 ms Table 110 Time delay on 8 pcs TONGAPC Characteristic Value Operate time accuracy 1 0 of the set value or 20 ms Generator and Interconnection Protection 1MRS758279 B REG615 Product version 5 0 FP1 60 ABB ...

Page 61: ...ng the Graphical Display Editor in PCM600 The user can create up to 10 SLD pages The local HMI includes a push button L R for local remote operation of the relay When the relay is in the local mode it can be operated only by using the local front panel user interface When the relay is in the remote mode it can execute commands sent from a remote location The relay supports the remote selection of ...

Page 62: ...e 17 Semi flush mounting 230 107 25 133 190 IECA070902 V4 EN Figure 18 Semi flush mounting in a 25º tilt 22 Relay case and plug in unit The relay cases are assigned to a certain type of plug in unit For safety reasons the relay cases for current measuring relays are provided with automatically operating contacts for short circuiting the CT secondary circuits when a relay unit is withdrawn from its...

Page 63: ...bracket for one relay in 4U Combiflex RHGT 19 variant C 2RCA022643P0001 19 rack mounting kit for one relay and one RTXP18 test switch the test switch is not included in the delivery 2RCA021952A0003 19 rack mounting kit for one relay and one RTXP24 test switch the test switch is not included in the delivery 2RCA022561A0003 Functional earthing flange for RTD modules1 2RCA036978A0001 Replacement kit ...

Page 64: ...bled via the local HMI The Web HMI functionality can be limited to read only access The relay connectivity package is a collection of software and specific relay information which enables system products and tools to connect and interact with the protection relay The connectivity packages reduce the risk of errors in system integration minimizing device configuration and setup times Further the co...

Page 65: ...ation configuration GOOSE communication configuration Phasor diagram viewing Event viewing Saving of event data on the user s PC Online monitoring Supported 26 Cyber security The relay supports role based user authentication and authorization It can store 2048 audit trail events to a non volatile memory The non volatile memory is based on a memory type which does not need battery backup or regular...

Page 66: ...inal diagrams GUID 4BA6AD56 1833 4BA6 B3CC 3C44FD9767BF V1 EN Figure 19 Terminal diagram of standard configuration A Generator and Interconnection Protection 1MRS758279 B REG615 Product version 5 0 FP1 66 ABB ...

Page 67: ...GUID 7E974B34 D8B8 4114 A24A 40F38BECF594 V1 EN Figure 20 Terminal diagram of standard configuration C Generator and Interconnection Protection 1MRS758279 B REG615 Product version 5 0 FP1 ABB 67 ...

Page 68: ...GUID 6756612D B6DA 4B52 822D B2794FADCC23 V1 EN Figure 21 Terminal diagram of standard configuration D Generator and Interconnection Protection 1MRS758279 B REG615 Product version 5 0 FP1 68 ABB ...

Page 69: ...45 Additional certificates can be found on the product page 29 References The www abb com substationautomation portal provides information on the entire range of distribution automation products and services The latest relevant information on the REG615 protection and control relay is found on the product page Scroll down the page to find and download the related documentation Generator and Interc...

Page 70: ...1 DEFLPDEF2 Io 2 67N 1 2 Directional earth fault protection high stage DEFHPDEF1 Io 1 67N 2 1 Transient intermittent earth fault protection INTRPTEF1 Io IEF 1 67NIEF 1 Negative sequence overcurrent protection NSPTOC1 I2 1 46 1 NSPTOC2 I2 2 46 2 Negative sequence overcurrent protection for machines MNSPTOC1 I2 M 1 46M 1 MNSPTOC2 I2 M 2 46M 2 Residual overvoltage protection ROVPTOV1 Uo 1 59G 1 ROVPT...

Page 71: ...rc protection ARCSARC1 ARC 1 50L 50NL 1 ARCSARC2 ARC 2 50L 50NL 2 ARCSARC3 ARC 3 50L 50NL 3 Multipurpose protection MAPGAPC1 MAP 1 MAP 1 MAPGAPC2 MAP 2 MAP 2 MAPGAPC3 MAP 3 MAP 3 MAPGAPC4 MAP 4 MAP 4 MAPGAPC5 MAP 5 MAP 5 MAPGAPC6 MAP 6 MAP 6 MAPGAPC7 MAP 7 MAP 7 MAPGAPC8 MAP 8 MAP 8 MAPGAPC9 MAP 9 MAP 9 MAPGAPC10 MAP 10 MAP 10 MAPGAPC11 MAP 11 MAP 11 MAPGAPC12 MAP 12 MAP 12 MAPGAPC13 MAP 13 MAP 13...

Page 72: ... Voltage unbalance VSQVUB1 PQUUB 1 PQVUB 1 Control Circuit breaker control CBXCBR1 I O CB 1 I O CB 1 Disconnector control DCXSWI1 I O DCC 1 I O DCC 1 DCXSWI2 I O DCC 2 I O DCC 2 Earthing switch control ESXSWI1 I O ESC 1 I O ESC 1 Disconnector position indication DCSXSWI1 I O DC 1 I O DC 1 DCSXSWI2 I O DC 2 I O DC 2 DCSXSWI3 I O DC 3 I O DC 3 Earthing switch indication ESSXSWI1 I O ES 1 I O ES 1 ES...

Page 73: ...IEC 61850 9 2 LE sampled value sending SMVSENDER SMVSENDER SMVSENDER IEC 61850 9 2 LE sampled value receiving voltage sharing SMVRCV SMVRCV SMVRCV Other Minimum pulse timer 2 pcs TPGAPC1 TP 1 TP 1 TPGAPC2 TP 2 TP 2 TPGAPC3 TP 3 TP 3 TPGAPC4 TP 4 TP 4 Minimum pulse timer 2 pcs second resolution TPSGAPC1 TPS 1 TPS 1 Minimum pulse timer 2 pcs minute resolution TPMGAPC1 TPM 1 TPM 1 Pulse timer 8 pcs P...

Page 74: ...PC 2 Analog value scaling SCA4GAPC1 SCA4 1 SCA4 1 SCA4GAPC2 SCA4 2 SCA4 2 SCA4GAPC3 SCA4 3 SCA4 3 SCA4GAPC4 SCA4 4 SCA4 4 Integer value move MVI4GAPC1 MVI4 1 MVI4 1 31 Document revision history Document revision date Product version History A 2016 05 20 5 0 FP1 First release B 2018 06 06 5 0 FP1 Content updated Generator and Interconnection Protection 1MRS758279 B REG615 Product version 5 0 FP1 74...

Page 75: ...75 ...

Page 76: ...and Phone 358 10 22 11 www abb com mediumvoltage www abb com substationautomation ABB Distribution Automation Maneja Works Vadodara 390013 India Phone 91 265 2604386 Fax 91 265 2638922 www abb com mediumvoltage www abb com substationautomation 1MRS758279 B Copyright 2018 ABB All rights reserved ...

Reviews: