Table 20. Electromagnetic compatibility tests
Description
Type test value
Reference
1 MHz/100 kHz burst disturbance test
IEC 61000-4-18
IEC 60255-26, class III
IEEE C37.90.1-2002
• Common mode
2.5 kV
• Differential mode
2.5 kV
3 MHz, 10 MHz and 30 MHz burst disturbance
test
IEC 61000-4-18
IEC 60255-26, class III
• Common mode
2.5 kV
Electrostatic discharge test
IEC 61000-4-2
IEC 60255-26
IEEE C37.90.3-2001
• Contact discharge
8 kV
• Air discharge
15 kV
Radio frequency interference test
10 V (rms)
f = 150 kHz...80 MHz
IEC 61000-4-6
IEC 60255-26, class III
10 V/m (rms)
f = 80...2700 MHz
IEC 61000-4-3
IEC 60255-26, class III
10 V/m
f = 900 MHz
ENV 50204
IEC 60255-26, class III
20 V/m (rms)
f = 80...1000 MHz
IEEE C37.90.2-2004
Fast transient disturbance test
IEC 61000-4-4
IEC 60255-26
IEEE C37.90.1-2002
• All ports
4 kV
Surge immunity test
IEC 61000-4-5
IEC 60255-26
• Communication
1 kV, line-to-earth
• Other ports
4 kV, line-to-earth
2 kV, line-to-line
Power frequency (50 Hz) magnetic field
immunity test
IEC 61000-4-8
• Continuous
• 1...3 s
300 A/m
1000 A/m
Pulse magnetic field immunity test
1000 A/m
6.4/16 µs
IEC 61000-4-9
Damped oscillatory magnetic field immunity test
IEC 61000-4-10
• 2 s
100 A/m
• 1 MHz
400 transients/s
Voltage dips and short interruptions
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
Generator and Interconnection Protection
1MRS758279 B
REG615
Product version: 5.0 FP1
ABB
29