Section 5

1MRS240173-IB B

4x Registers

 46

REF615R

DPU2000R Modbus Point List Mitigation Manual

Table 20:

Mitigation of Modbus mapping for fault records block

DPU2000R 

register addr.

DPU 2000R 

description

Scale

REF615R 

register 

addr.

Scale

IEC 61850 path

Comments on REF615R 

Modbus points mapping

41409

Data Control 

1=First record; 

2=Next record; 

3=Oldest 

Unreported record

1

41409

1

 

Data Control 1=First record; 

2=Next record; 3=Oldest 

Unreported record

41410

Fault type element

1

41410

1

LD0.FLTMSTA1.ProFcn.stVal

 Protection function, see table 

7.1 from “Feeder Protection 

and Control REF615R Modbus 

Point List Manual” 

(1MRS240052-IB) 

41411

Active set and recl. 

Seq.

1

41463

1

LD0.FLTMSTA1.ActSG.stVal

Active setting group

41464

LD0.FLTMSTA1.ShotPntr.stVal

Auto reclosing shot pointer 
value Au

41412

Fault number

1

41412

1

 

Fault number after device 

powers up, it does not count 

fault records saved before 

power up. 

41413

Year

1

41413

1

 

Year

41414

Month

1

41414

1

 

Month

41415

Day

1

41415

1

 

Day

41416

Hours

1

41416

1

 

Hours

41417

Minutes

1

41417

1

 

Minutes

41418

Seconds

1

41418

1

 

Seconds

41419

Hundredths of 

Seconds

1

41419

1

 

Hundredths of Seconds

41420

Ia (Scale at 

register 41424)

1

41420

 100

LD0.FLTMSTA1.AmpsA.mag.f

reading per unit value by 

default

41421

Ib (Scale at 

register 41424)

1

41421

 100

LD0.FLTMSTA1.AmpsB.mag.f

reading per unit value by 

default

41422

Ic (Scale at register 

41424)

1

41422

 100

LD0.FLTMSTA1.AmpsC.mag.f

reading per unit value by 

default

41423

In (Scale at 

register 41424)

1

41423

 100

LD0.FLTMSTA1.AmpsN.mag.f

reading per unit value by 

default

41424

Current ( I ) Scale x

1

41424

 1

 

100 by default

41425

Ia Angle

1

 

 

 

N/A in REF615R

41426

Ib Angle

1

 

 

 

N/A in REF615R

41427

Ic Angle

1

 

 

 

N/A in REF615R

41428

In Angle

1

 

 

 

N/A in REF615R

41429

Zero Seq I (Mag)

1

 

 

 

 

41430

Pos Seq I (Mag)

1

41430

 100

LD0.FLTMSTA1.AmpsPsSeq.mag.f

 

41431

Neg Seq I (Mag)

1

41431 

 100

LD0.FLTMSTA1.AmpsNgSeq.mag.f

 

41432

Zero Seq I (Ang)

1

 

 

 

N/A in REF615R

41433

Pos Seq I (Ang)

1

 

 

 

N/A in REF615R

41434

Neg Seq I (Ang)

1

 

 

 

N/A in REF615R

Summary of Contents for RELION REF615R

Page 1: ...B Relion Protection and Control REF615R DPU2000R Modbus Point List Mitigation Manual...

Page 2: ......

Page 3: ...Document ID 1MRS240173 IB Issued 09 24 2016 Revision B Product version 4 1 Copyright 2016 ABB All rights reserved...

Page 4: ...osed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of ABB Group All other brand or product names mentioned in this document may be trademarks or...

Page 5: ...ace which should be connected to a secure network It is sole responsibility of person or entity responsible for network administration to ensure a secure connection to the network and to establish and...

Page 6: ...cal equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN...

Page 7: ...ion 19 Section 4 1x Registers 21 Function code 2 Read input status 21 Logical input block single bit data 21 Physical input block Single bit data 24 Logical Input Block Double bit data with momentary...

Page 8: ...ce Alarm 50 1D 53 2nd Instantaneous Over current Distance Alarm 50 2D 53 Phase Over current Disabled Alarm PH3 D 53 Ground Over current Disabled Alarm GRD D 53 Three Phase Under voltage Trip 27 3P 53...

Page 9: ...for the logical input block in double bit block 25 Table 8 Mitigations of Modbus registers mapping for the physical input block in double bit block 26 Section 5 4x Registers 27 Table 9 Mitigations of...

Page 10: ...20 Mitigation of Modbus mapping for fault records block 46 Table 21 Mitigation of Modbus mapping for operation records 48 Table 22 One example of Modbus event record value 48 Section 6 6x Registers 5...

Page 11: ...to 40001 00 28 Figure 3 UDR multiplicative scaling factor for LD0 CMMXU1 A phsA instCVal mag f 29 Figure 4 UDR divisor scaling factor to convert a voltage reading from pu to primary KV 30 Figure 5 Sn...

Page 12: ...Section 1MRS240173 IB B 6 REF615R DPU2000R Modbus Point List Mitigation Manual...

Page 13: ...tion system engineer or system integrator responsible for pre engineering and engineering for communication setup in a substation 1 3 Document revision history 1 4 Related documentation Document revis...

Page 14: ...aded process performance leading to personal injury or death Therefore comply fully with all warning and caution notices The caution icon indicates important information or warning related to the conc...

Page 15: ...on top of it it still supports other well respected digital communication protocols such as Modbus and DNP3 To reduce a system integrator s efforts to remap the Modbus point list after substituting a...

Page 16: ...IB B Modbus point list mapping mitigations 10 REF615R DPU2000R Modbus Point List Mitigation Manual REF615R please refer to the Feeder Protection and Control REF615R Modbus Point List Manual with Docum...

Page 17: ...F615R their original Modbus address assignments are reversed 3 1 1 Logical output block Single bit data REF615R maps the single bit logical output points in the same register assignments and sequence...

Page 18: ...1 14 LD0 PHPTOV1 Op general 15 Direct Over current Trip Positive Sequence 67P 1 15 LD0 DPHLPTOC1 Op general 16 Direct Over current Trip Negative Sequence 67N 16 LD0 DEFLPTOC1 Op general 17 Frequency...

Page 19: ...larm 32 NA 43 LD0 DNZSRDIR1 Dir general 44 Three Phase Under voltage Trip 27 3P See Section 7 1 5 for example or explanation 45 3 Phase KVAR Demand Alarm VARDA N A in REF615R 46 Recloser Counter Alarm...

Page 20: ...8 TRIP B Single Phase Trip Phase B TRIP B latch See Section 7 1 6 for example or explanation 69 TRIP C Single Phase Trip Phase C TRIP C latch See Section 7 1 6 for example or explanation 70 User Logic...

Page 21: ...xplanation 101 Phase Power Directional Alarm positive sequence 32P 2 Please reference REF615R 0x address of 42 as it is mapped for 32 PA 102 Phase Power Directional Alarm negative sequence 32N 2 Pleas...

Page 22: ...Distance Zone 2 21P 2 N A in REF615R 132 Phase Distance Zone 2 Latched 21P 2 latch N A in REF615R 133 Phase Distance Zone 3 21P 3 N A in REF615R 134 Phase Distance Zone 3 Latched 21P 3 latch N A in R...

Page 23: ...164 Negative Sequence Time Over current Trip Alarm 46A 164 LD0 NSPTOC2 Op general 165 Negative Sequence Time Over current Trip Alarm 46A latch See Section 7 1 6 for example or explanation 166 Local Re...

Page 24: ...card 259 Reserved Status 259 Normal speed BIO card 275 High speed BIO card 260 Reserved Status 260 Normal speed BIO card 276 High speed BIO card 261 Reserved Status 261 Normal speed BIO card 277 High...

Page 25: ...615R supports high speed BIO cards which are not available in DPU2000R the ending coil address for this block extends to 1088 270 OUT 1 Status 270 LD0 XUGGIO110 SPCSO1 stVal Normal speed BIO card 86 L...

Page 26: ...scription REF615R register addr IEC 61850 path Comments on REF615R Modbus points mapping 1025 Reserved Status 1025 Normal speed BIO card 1057 High speed BIO card 1026 Reserved Momentary 1026 Normal sp...

Page 27: ...dress assignments are reversed 4 1 1 Logical input block single bit data REF615R maps the single bit logical input points in the same register assignments and sequence as in DPU2000R Table 5 Mitigatio...

Page 28: ...ple or explanation 10015 Initiate Event Capture 1 ECI1 N A in REF615R 10016 Initiate Event Capture 2 ECI2 N A in REF615R 10017 Waveform Capture Initiate WCI DR RDRE1 RcdTrg stVal 10018 Enable Zone Seq...

Page 29: ...t LIS5 10049 LD0 SRGAPC1 Set5 stVal 10050 Latched Input 6 Set LIS6 10050 LD0 SRGAPC1 Set6 stVal 10051 Latched Input 7 Set LIS7 10051 LD0 SRGAPC1 Set7 stVal 10052 Latched Input 8 Set LIS8 10052 LD0 SRG...

Page 30: ...rmal speed BIO card 10273 High speed BIO card 10258 IN12 Reserved 10258 Normal speed BIO card 10274 High speed BIO card 10259 IN11 Reserved 10259 Normal speed BIO card 10293 LD0 XAUGGIO130 Ind11 stVal...

Page 31: ...BIO card 10271 52b reserved status 10271 Normal speed BIO card 10287 High speed BIO card 10272 52a reserved status 10272 Normal speed BIO card 10288 High speed BIO card DPU2000R register addr DPU 2000...

Page 32: ...ds to 11102 The IEC61850 path for the status points are the same as in the physical input block with single bit data In REF615R MCD Momentary Change Detect bits are implemented and mapped in the same...

Page 33: ...R view In REF615R user can reassign the signal to its new bit address using CMT UDR tool As Figure 1 shows user can highlight the signal of 51P 3I PHLPTOC1 1 Trip 51P Trip from the left pane then expa...

Page 34: ...to UDR one can pick up the signal from either of the other two options 5 1 1 2 Example of remapping an analog register to UDR The purposes of remapping the analog measurement signals are often to chan...

Page 35: ...e right pane and click on Go to right button to move the signal to the right pane c If the primary CT rating is 600A and if the original signal s scale factor keeps default value of 100 user only need...

Page 36: ...Mitigations of Modbus system status configuration block If the original signal is mapped into 32 bit the UDR shall keep it as 32 bit register by leaving the next register as Empty Register DPU2000R r...

Page 37: ...kWhr kVARhr 1 MWhr MVARhr 40132 0 0 Wye PT 1 Delta PT 40132 0 0 Wye PT 1 Delta PT 40133 142 Catalog Number 40133 141 LD0 LPHD1 PhyNam eOrdNum replaced by order code 40143 CPU software version number...

Page 38: ...7 Spare Spare 40170 6 1 One or More Unreported Operations Records 40170 6 1 One or More Unreported Operations Records 40170 5 40170 0 Division code 00101 binary N A in REF615R 40171 15 40171 10 Produc...

Page 39: ...le 12 Mitigations of Modbus mappings for RMS load current angular values block REF615R provides another set of 6 system status registers SSR1 SSR2 SSR3 SSR4 SSR5 SSR6 REF615R also provides device info...

Page 40: ...W phsA instCVal mag f 40285 286 kWatts B 1 40285 286 1 LD0 SPEMMXU1 W phsB instCVal mag f 40287 288 kWatts C 1 40287 288 1 LD0 SPEMMXU1 W phsC instCVal mag f 40289 290 3 Phase kWatts 1 40289 290 1 LD0...

Page 41: ...ve Sequence Voltage Magnitude 1 40321 322 100 LD0 VSMSQI1 SeqV c1 instCVal mag f reading per unit value by default 40323 Positive Sequence Voltage Angle 1 40323 1 LD0 VSMSQI1 SeqV c1 instCVal ang f 40...

Page 42: ...0R description Scale REF615R register addr Scale IEC 61850 path Comments on REF615R Modbus points mapping DPU2000R register addr DPU2000R description Scale REF615R register addr Scale IEC61850 path Co...

Page 43: ...ault 40518 Peak Demand Current B Year Month 40518 LD0 CMSTA1 MaxAmpsB t Year Month 40519 Peak Demand Current B Day Hour 40519 Day Hour 40520 Peak Demand Current B Minute 40520 Minute 40521 Peak Demand...

Page 44: ...40549 1 LD0 SPEMSTA1 MaxVArPhsA mag f 40551 Peak Demand KVARs A Year Month 40551 LD0 SPEMSTA1 MaxVArPhsA t Year Month 40552 Peak Demand KVARs A Day Hour 40552 Day Hour 40553 Peak Demand KVARs A Minut...

Page 45: ...value by default 40650 Minimum Demand Current C Year Month 40650 LD0 CMSTA1 MinAmpsC t Year Month 40651 Minimum Demand Current C Day Hour 40651 Day Hour 40652 Minimum Demand Current C Minute 40652 Min...

Page 46: ...0684 LD0 SPEMSTA1 MinVArPhsB t Year Month 40685 Minimum Demand KVARs B Day Hour 40685 Day Hour 40686 Minimum Demand KVARs B Minute 40686 Minute 40687 Minimum Demand KVARs C 1 40687 1 LD0 SPEMSTA1 MinV...

Page 47: ...42010 100 LD0 SSCBR1 AccAPwrPhA mag f Can be used for Sum of fault current A 40772 Sum of fault current B 1 42012 100 LD0 SSCBR1 AccAPwrPhB mag f Can be used for Sum of fault current B 40773 Sum of f...

Page 48: ...oltage Trip any single phase 59 1 40897 2 LD0 PHPTOV1 Op general 40897 1 Direct Over current Trip Positive Sequence 67P 1 40897 1 LD0 DPHLPTOC1 Op general 40897 0 Direct Over current Trip Negative Seq...

Page 49: ...5 C5 41187 8 LD0 SPCGGIO3 SPCSO5 Oper ctlVal Control button 5 C5 set 41187 9 Control button 5 C5 reset 41159 6 Control button 4 C4 41187 6 LD0 SPCGGIO3 SPCSO4 Oper ctlVal Control button 4 C4 set 41187...

Page 50: ...4 411 95 Set Reset command registers 41214 41 223 LD0 SRGAPC1 2 Rs1 8 Oper ctlVal and LD0 SRGAPC3 4 Rs1 8 Oper ctlVal Totally 2 blocks of set reset control commands Each block has 16 control points 41...

Page 51: ...4 Oper ctlVal High speed BIO card need to set relay in test mode and remote mode 41201 4 OUT3 41207 4 LD0 XUGGIO100 SPCSO3 Oper ctlVal Normal speed BIO card need to set relay in test mode and remote m...

Page 52: ...e power up 41413 Year 1 41413 1 Year 41414 Month 1 41414 1 Month 41415 Day 1 41415 1 Day 41416 Hours 1 41416 1 Hours 41417 Minutes 1 41417 1 Minutes 41418 Seconds 1 41418 1 Seconds 41419 Hundredths of...

Page 53: ...q V Ang 1 N A in REF615R 41445 Fault Location 10 41445 LD0 FLTMSTA1 FltDisKm mag f Distance to fault measured in pu 41446 41447 fault impedance real 1000 41446 41448 1000 LD0 FLTMSTA1 FltZ cVal mag f...

Page 54: ...from PCM6000 CMT by simply checking off the event enable bit as shown in Figure 6 DPU2000R register addr DPU 2000R description Scale REF615R register addr Scale Comments on REF615R Modbus points mappi...

Page 55: ...Manual Figure 6 Snapshot of using CMT to enable Modbus event on coil address 587 Only configure points with double bits for event configurations using PCM600 CMT It is because Modbus server only gene...

Page 56: ...Section 5 1MRS240173 IB B 4x Registers 50 REF615R DPU2000R Modbus Point List Mitigation Manual...

Page 57: ...ion 6 6x Registers REF615R 51 DPU2000R Modbus Point List Mitigation Manual Section 6 6x Registers 6x registers are not available in REF615R REF615R provides WebHMI and PCM600 CMT tools to make setting...

Page 58: ...Section 6 1MRS240173 IB B 6x Registers 52 REF615R DPU2000R Modbus Point List Mitigation Manual...

Page 59: ...certain protection functions 7 1 3 Phase Over current Disabled Alarm PH3 D N A in the current release But the solution may be provided in the future release by either adding more Modbus mapping points...

Page 60: ...atus of the blocking signals which are configured from the PCM600 ACT logics to block the certain protection functions 7 2 Logical input ACT logic selected examples 7 2 1 Enable phase over current pro...

Page 61: ...ions or by reading the status of the blocking signals which are configured from the PCM600 ACT logics to block the certain protection functions 7 2 5 Enable 50P 3 and 50N 3 50 3 N A in the current rel...

Page 62: ...Section 7 1MRS240173 IB B Selected PCM ACT logic examples or explanations 56 REF615R DPU2000R Modbus Point List Mitigation Manual...

Page 63: ...er DNP3 A distributed network protocol originally developed by Westronic The DNP3 Users Group has the ownership of the protocol and assumes responsibility for its evolution DPC Double point control DP...

Page 64: ...r Setting tool in PCM600 REF615R Wire alike replacement option for DPU2000R with the same form factor SBO Select before operate SSR1 System status register for device health SSR2 System status registe...

Page 65: ......

Page 66: ...stribution Automation 4300 Coral Ridge Drive Coral Springs FL 33065 USA Phone 1 800 523 2620 Phone 1 954 752 6700 Fax 1 954 345 5329 www abb com substationautomation 1MRS240173 IB B Copyright 2016 ABB...

Reviews: