Section 3
1MRS240173-IB B
0x registers
12
REF615R
DPU2000R Modbus Point List Mitigation Manual
2
Breaker is Closing
(Close)
2
LD0.MVGAPC8.Q3.stVal
Configured by PCM600
ACT.
3
DPU is in ALARM (ALARM)
3
LD0.LLN0.Health.stVal
Converted enum value to
boolean to read ALARM
as same in DPU2000R.
4
Under voltage Trip
(27-1P)
4
LD0.PHPTUV1.Op.general
5
Negative Sequence Over-current Trip (46)
5
LD0.NSPTOC1.Op.general
6
Phase Instantaneous Over-current Trip
(50P1)
6
LD0.PHHPTOC1.Op.general
7
Neutral Instantaneous Over-current Trip
(50N1)
7
LD0.EFHPTOC3.Op.general
8
Phase Instantaneous Over-current Trip
(50P2)
8
LD0.PHHPTOC2.Op.general
9
Neutral Instantaneous Over-current Trip
(50N2)
9
LD0.EFHPTOC4.Op.general
10
Phase Instantaneous Over-current Trip
(50P3)
10
LD0.PHIPTOC1.Op.general
11
Neutral Instantaneous Over-current Trip
(50N3)
11
LD0.EFIPTOC2.Op.general
12
Phase Time Over-current Trip (51P)
12
LD0.PHLPTOC1.Op.general
13
Neutral Time Over-current Enabled (51N)
13
LD0.EFLPTOC2.Op.general
14
Overvoltage Trip any single phase (59-1)
14
LD0.PHPTOV1.Op.general
15
Direct Over-current Trip Positive Sequence
(67P-1)
15
LD0.DPHLPTOC1.Op.general
16
Direct Over-current Trip Negative Sequence
(67N)
16
LD0.DEFLPTOC1.Op.general
17
Frequency Shed (1st Stage) (81S-1)
17
LD0.LSHDPTRC1.Op.general
18
Frequency Restore (1st Stage) (81R-1)
18
LD0.LSHDPTRC1.RestLodOp.general
19
! Phase A Target Alarm (PATA)
2332
! LD0.LEDGGIO1.ISCSO1.stVal
! Address different in
REF615R
20
! Phase B Target Alarm (PBTA)
2334
! LD0.LEDGGIO1.ISCSO2.stVal
! Address different in
REF615R
21
! Phase C Target Alarm (PCTA)
2336
! LD0.LEDGGIO1.ISCSO3.stVal
! Address different in
REF615R
22
Trip Coil Failure Alarm (TCFA)
22
LD0.MVGAPC8.Q1.stVal
Configured by PCM600
ACT.
23
Tap Changer Cutoff (TCC)
23
LD0.DARREC1.ActRec.stVal
24
Reclosing Disabled Alarm (79DA)
Please reference
REF615R 1x address of
10034 as it is mapped for
43a.
25
Pick Up Alarm (PUA)
25
LD0.LEDPTRC1.Str.general
26
Recloser Lock Out Alarm (79LOA)
26
LD0.DARREC1.LO.stVal
27
Breaker Fail Alarm (BFA)
27
LD0.SSCBR1.OpnAlm.stVal
28
Phase Demand Current Alarm (PDA)
N/A in REF615R
29
Neutral Demand Current Alarm (NDA)
N/A in REF615R
DPU2000R
register
addr.
DPU 2000R description
REF615R
register
addr.
IEC 61850 path
Comments on REF615R
Modbus points mapping
Summary of Contents for RELION REF615R
Page 1: ...B Relion Protection and Control REF615R DPU2000R Modbus Point List Mitigation Manual...
Page 2: ......
Page 12: ...Section 1MRS240173 IB B 6 REF615R DPU2000R Modbus Point List Mitigation Manual...
Page 56: ...Section 5 1MRS240173 IB B 4x Registers 50 REF615R DPU2000R Modbus Point List Mitigation Manual...
Page 58: ...Section 6 1MRS240173 IB B 6x Registers 52 REF615R DPU2000R Modbus Point List Mitigation Manual...
Page 65: ......