1MRS240173-IB B
Section 3
0x registers
REF615R
13
DPU2000R Modbus Point List Mitigation Manual
30
Blown Fuse Alarm (BFUA)
30
LD0.SEQRFUF1.Str.general
31
Kilo amperes Symmetrical Inverted Alarm
(KSI)
31
LD0.SSCBR1.APwrAlm.stVal
32
Recloser Counter Alarm 1 (79CA1)
32
LD0.SSCBR1.OpNumAlm.stVal
33
High Power Factor Alarm (HPFA)
N/A in REF615R
34
Low Power Factor Alarm (LPFA)
N/A in REF615R
35
Over-current Trip Counter Alarm (OCTC)
N/A in REF615R
36
1st Instantaneous Over-current Distance
Alarm (50-1D)
See Section 7.1.1 for
example or explanation
37
2nd Instantaneous Over-current Distance
Alarm (50-2D)
See Section 7.1.2 for
example or explanation
38
Settings Table Change Alarm (STC)
38
LD0.LLN0.SetChg.stVal
39
Zone Sequence Control Alarm (ZSC)
39
LD0.DARREC1.ProCrd.stVal
40
Phase Over-current Disabled Alarm
(PH3-D)
See Section 7.1.3 for
example or explanation
41
Ground Over-current Disabled Alarm
(GRD-D)
See Section 7.1.4 for
example or explanation
42
PA (67P) Positive Sequence Direct
Over-current Trip Alarm
(32 PA)
42
LD0.DPSRDIR1.Dir.general
43
PN (67N) Negative Sequence Direct
Over-current Trip Alarm
(32 NA)
43
LD0.DNZSRDIR1.Dir.general
44
Three Phase Under voltage Trip (27-3P)
See Section 7.1.5 for
example or explanation
45
3 Phase KVAR Demand Alarm (VARDA)
N/A in REF615R
46
Recloser Counter Alarm 2 (79CA2)
N/A in REF615R
! 47
A Single Phase Trip (Phase A) (TRIP A)
! 19
! LD0.LEDPTRC1.Op.phsA
! Address different in
REF615R
! 48
B Single Phase Trip (Phase B) (TRIP B)
! 20
! LD0.LEDPTRC1.Op.phsB
! Address different in
REF615R
! 49
C Single Phase Trip (Phase C) (TRIP C)
! 21
! LD0.LEDPTRC1.Op.phsC
! Address different in
REF615R
50
Under voltage Trip
(27-1 latch)
See Section 7.1.6 for
example or explanation
51
Negative Sequence Over-current Trip
(46 latch)
See Section 7.1.6 for
example or explanation
52
Phase Instantaneous Over-current Trip
(50P1 latch)
See Section 7.1.6 for
example or explanation
53
Neutral Instantaneous Over-current Trip
(50N1 latch)
See Section 7.1.6 for
example or explanation
54
Phase Instantaneous Over-current Trip
(50P2 latch)
See Section 7.1.6 for
example or explanation
55
Neutral Instantaneous Over-current Trip
(50N2 latch)
See Section 7.1.6 for
example or explanation
56
Phase Instantaneous Over-current Trip
(50P3 latch)
See Section 7.1.6 for
example or explanation
DPU2000R
register
addr.
DPU 2000R description
REF615R
register
addr.
IEC 61850 path
Comments on REF615R
Modbus points mapping
Summary of Contents for RELION REF615R
Page 1: ...B Relion Protection and Control REF615R DPU2000R Modbus Point List Mitigation Manual...
Page 2: ......
Page 12: ...Section 1MRS240173 IB B 6 REF615R DPU2000R Modbus Point List Mitigation Manual...
Page 56: ...Section 5 1MRS240173 IB B 4x Registers 50 REF615R DPU2000R Modbus Point List Mitigation Manual...
Page 58: ...Section 6 1MRS240173 IB B 6x Registers 52 REF615R DPU2000R Modbus Point List Mitigation Manual...
Page 65: ......