HMI Signal Name:
Status
Description
RTC
READY / FAIL
This signal will be active when there is a
hardware error with the real time clock.
Time Sync
READY / FAIL
This signal will be active when the
source of the time synchronization is
lost, or when the time system has to
make a time reset.
Application
READY / FAIL
This signal will be active if one or more
of the application threads are not in the
state that Runtime Engine expects. The
states can be CREATED, INITIALIZED,
RUNNING, etc.
RTE
READY / FAIL
This signal will be active if the Runtime
Engine failed to do some actions with the
application threads. The actions can be
loading of settings or parameters for
components, changing of setting groups,
loading or unloading of application
threads.
IEC61850
READY / FAIL
This signal will be active if the IEC 61850
stack did not succeed in some actions
like reading IEC 61850 configuration,
startup etc.
LMD
READY / FAIL
LON network interface, MIP/DPS, is in
an unrecoverable error state.
LDCMxxx
READY / FAIL
Line Differential Communication Error
status
OEM
READY / FAIL
Optical Ethernet Module error status
Also the internal signals, such as INT--FAIL and INT--WARNING can be
connected to binary output contacts for signalling to a control room.
In the IED Status - Information, the present information from the self-supervision
function can be viewed. Indications of failure or warnings for each hardware
module are provided, as well as information about the external time
synchronization and the internal clock. All according to table
synchronization can be considered as a warning only. The IED has full
functionality without time synchronization.
13.2.2
Using front-connected PC
M11763-203 v5
When an internal fault has occurred, extensive information about the fault can be
retrieved from the list of internal events available in the SMS part:
TRM-STAT TermStatus - Internal Events
The list of internal events provides valuable information, which can be used during
commissioning and fault tracing.
The internal events are time tagged with a resolution of 1ms and stored in a list.
The list can store up to 40 events. The list is based on the FIFO principle, when it is
1MRK 505 372-UEN A
Section 13
Troubleshooting
Busbar protection REB670 2.2 IEC
173
Commissioning manual