Table 7. Power supply
Description
PSM02
PSM03
U
aux
nominal
48-125 V DC
100, 110, 120, 220, 240V AC 50/60Hz
110, 125, 220, 250V DC
U
aux
variation
80...120% of Un (38.4...150 V DC)
80...120% of Un (88...300 V DC)
80...115% of Un (80...276 V AC)
Maximum load of auxiliary voltage
supply
35 W for DC
40 VA for AC
Ripple in the DC auxiliary voltage
Max 15% of the DC value (at frequency of 100 and 120 Hz)
Maximum interruption time in the
auxiliary DC voltage without
resetting the IED
50 ms at U
aux
IEC 60255-11 (1979), VDE 0435, Part 303
Table 8. Binary input
Description
Value
Operating range
Maximum input voltage 300 V DC
Rated voltage
24...250 V DC
Current drain
1.6...1.8 mA
Power consumption/input
<0.38 W
Threshold voltage
24, 48, 60, 110, 125, 220 and 250V DC
Table 9. Precision binary input
Description
Value
Operating range
Maximum input voltage 300 V DC
Rated voltage
33...288 V DC
Current drain
0...0.5 mA
Power consumption/input
<0.15 W
Threshold voltage
24, 48, 60, 110, 125, 220 and 250V DC
Table 10. Signal output and IRF
1)
output
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
10 A
Make and carry 0.5 s
30 A
Breaking capacity when the control-circuit time constant
L/ R<40 ms, at U< 48/110/220 V DC
≤
0.5 A/
≤
0.1 A/
≤
0.04 A
1) Internal fault relay – change over contact
Summary of Contents for Relion REB500