8.3.1
Identification
M14887-1 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Instantaneous residual overcurrent
protection
EFPIOC
IN>>
IEF V1 EN-US
50N
8.3.2
Application
M12699-3 v5
In many applications, when fault current is limited to a defined value by the object impedance,
an instantaneous earth-fault protection can provide fast and selective tripping.
The Instantaneous residual overcurrent EFPIOC, which can operate in 15 ms (50 Hz nominal
system frequency) for faults characterized by very high currents, is included in the IED.
8.3.3
Setting guidelines
IP14985-1 v1
M12762-44 v2
M12762-4 v4
The parameters for the Instantaneous residual overcurrent protection EFPIOC are set via the
local HMI or PCM600.
Some guidelines for the choice of setting parameter for EFPIOC is given.
M12762-6 v7
GlobalBaseSel: Selects the global base value group used by the function to define (IBase),
(
UBase) and (SBase).
The setting of the function is limited to the operate residual current to the protection (
IN>>).
The basic requirement is to assure selectivity, that is EFPIOC shall not be allowed to operate
for faults at other objects than the protected object (line).
For a normal line in a meshed system single phase-to-earth faults and phase-to-phase-to-earth
faults shall be calculated as shown in figure
0
) to
the protection are calculated. For a fault at the remote line end this fault current is I
fB
. In this
calculation the operational state with high source impedance Z
A
and low source impedance Z
B
should be used. For the fault at the home busbar this fault current is I
fA
. In this calculation the
operational state with low source impedance Z
A
and high source impedance Z
B
should be
used.
~
~
Z
A
Z
B
Z
L
A
B
IED
I
fB
Fault
IEC09000022-1-en.vsd
IEC09000022 V1 EN-US
Figure 270: Through fault current from A to B: I
fB
1MRK 505 343-UEN B
Section 8
Current protection
415
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...