5.1. Make connections between the signals that the server is sending and the
GOOSE receive interface function blocks (GOOSEBINRCV and
GOOSEINTLKRCV) on the client’s side.
If a client is defined for GOOSE receive then at least one cross
in SMT is required to be able to write the configuration to the
IED.
Be sure to set the setting
Operation
for GOOSEBINRCV and
GOOSEINTLKRCV to
On
in PST to enable GOOSE
communication.
6. Write the configuration to the IED, see
Note that the engineered data is written to the IED when
executing a common
Write to IED
operation.
Section 7
1MRK511240-UEN B
IEC 61850 communication engineering
78
670 series
Engineering Manual