M12342-1 v21
Table 49. Directional phase overcurrent protection, four steps OC4PTOC
Function
Range or value
Accuracy
Operate current, step 1-4
(5-2500)% of
lBase
±
1.0% of I
r
at I ≤ I
r
±
1.0% of I at I > I
r
Reset ratio
> 95% at (50–2500)% of
lBase
-
Minimum operate current, step 1-4
(1-10000)% of
lBase
±
1.0% of I
r
at I ≤ I
r
±
1.0% of I at I > I
r
Relay characteristic angle (RCA)
(40.0–65.0) degrees
±
2.0 degrees
Relay operating angle (ROA)
(40.0–89.0) degrees
±
2.0 degrees
Second harmonic blocking
(5–100)% of fundamental
±
2.0% of I
r
Independent time delay at 0 to 2 x I
set
, step
1-4
(0.000-60.000) s
±
0.2% or
±
35 ms whichever is greater
Minimum operate time for inverse curves ,
step 1-4
(0.000-60.000) s
±0.2% or ±35 ms whichever is greater
Inverse time characteristics, see table
16 curve types
Operate time, start non-directional at 0 to
2 x I
set
Min. = 15 ms
-
Max. = 30 ms
Reset time, start non-directional at 2 x I
set
to 0
Min. = 15 ms
-
Max. = 30 ms
Operate time, start non-directional at 0 to
10 x I
set
Min. = 5 ms
Max. = 20 ms
-
Reset time, start non-directional at 10 x I
set
to 0
Min. = 20 ms
Max. = 35 ms
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Impulse margin time
15 ms typically
-
Operate frequency, directional overcurrent
38-83 Hz
-
Operate frequency, non-directional
overcurrent
10-90 Hz
-
1MRK 504 155-BEN F
Transformer protection RET670 2.1 IEC
76
ABB