Maximum 176 binary input channels
may be activated simultaneously with
influencing factors within nominal
range.
The stated operate time for functions
include the operating time for the
binary inputs and outputs.
M50609-2 v9
Table 13. BIM - Binary input module with enhanced pulse counting capabilities
Quantity
Rated value
Nominal range
Binary inputs
16
-
DC voltage, RL
24/30 V
48/60 V
110/125 V
220/250 V
RL
±
20%
RL
±
20%
RL
±
20%
RL
±
20%
Power consumption
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
-
Counter input frequency
10 pulses/s max
-
Balanced counter input frequency
40 pulses/s max
-
Oscillating signal discriminator
Blocking settable 1–40 Hz
Release settable 1–30 Hz
*Debounce filter
Settable 1-20 ms
Binary input operate time
(Debounce filter set to 0 ms)
3 ms
-
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
1MRK 504 155-BEN F
Transformer protection RET670 2.1 IEC
ABB
53