a) Z locus in under excitation for heavily loaded machine
b) Z locus in under excitation for lightly loaded machine
c) Z locus for a fault in the network
X (Reactance)
R (Resistance)
-X
Relay operation
characteristics
-R
a
b
c
GUID-C7940DC8-04A8-4FED-B089-DAA9B21D50DB V2 EN
Figure 349:
Typical impedance locus in underexcitation: a) heavy load b) light load c)
fault in the network
4.7.2.6
Signals
Table 606:
40 Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
I
1
SIGNAL
0
Positive sequence current
V_A_AB
SIGNAL
0
Phase-to-ground voltage A or phase-to-phase voltage
AB
V_B_BC
SIGNAL
0
Phase-to-ground voltage B or phase-to-phase voltage
BC
V_C_CA
SIGNAL
0
Phase-to-ground voltage C or phase-to-phase voltage
CA
V
1
SIGNAL
0
Positive phase sequence voltage
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
EXT_LOS_DET
BOOLEAN
0=False
External signal for excitation loss detection
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
703
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......