Figure 325:
Tripping curve of "OvExt IDMT Crv2" based on the settings specified in
example 3. The two dots marked on the curve are referred to in the text.
If the excitation level stays at 1.26, the tripping occurs after 26.364 s as per the marked dot
in
. For the excitation level of 1.4, the second dot in
, the curve
"OvExt IDMT Crv2" gives 0.2636 s as per
Equation
, but the
Minimum trip time
setting
limits the trip time to 1.0 s.
The
Maximum trip time
setting limits the trip time to 1000 s if the
excitation level stays between 1.1 and 1.16.
In general, however, the excitation level seldom remains constant.
Therefore, the exact trip times in any inverse time mode are difficult to
predict.
Example 4
In this case, the function operation is according to IDMT. The
Operating curve type
setting is selected as "OvExt IDMT Crv4". The corresponding example settings for the