![ABB Relion 615 series Point List Manual Download Page 39](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_point-list-manual_3388490039.webp)
2.5.1
System functions
2.5.1.1
CTRL.LLN0 Local remote station off
Table 74:
CTRL.LLN0 Local remote station off
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
CTRL.LLN0
.LocRem.stVal
-
Off=0; Loc=1; Rem=2;
Station=3
0…3
R
0,3,0,3
2.5.1.2
LD0.LPHD1 System values
Table 75:
LD0.LPHD1 System values
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
LD0.LPHD1
.NumCmpChg.stVal
-
Num.of comp. changes
0…65535
R
0,65535,0,65535
.NumPwrUp.stVal
-
Num.of power ups
0…65535
R
0,65535,0,65535
.PhyHealth1.stVal
Warning
Warning code
0…65535
R
0,65535,0,65535
.PhyHealth2.stVal
Internal Fault
Internal fault code
0…65535
R
0,65535,0,65535
.WacTrg.stVal
-
Num.of watchdog resets
0…65535
R
0,65535,0,65535
.WrmStr.stVal
-
Num.of warm starts
0…65535
R
0,65535,0,65535
2.5.1.3
LD0.DNPGGIO1 Active parameter setting group
Table 76:
LD0.DNPGGIO1 Active parameter setting group
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
LD0.DNPGGIO1
.ActSG.stVal
-
Active setting group
1…6
R
1,6,1,6
2.5.1.4
LD0.LEDGGIO1 LHMI LED indications (3 states)
Table 77:
LD0.LEDGGIO1 LHMI LED indications (3 states)
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
LD0.LEDGGIO1
.ISCSO1.stVal
-
LED 1 state
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
.ISCSO2.stVal
-
LED 2 state
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
.ISCSO3.stVal
-
LED 3 state
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
.ISCSO4.stVal
-
LED 4 state
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
Table continues on next page
1MRS756879 D
Section 2
DNP3 data mappings
RED615
33
Point List Manual