2.3.2.3
CTRL.Dxxxxx2 Controllable disconnector (2)
Table 8:
CTRL.Dxxxxx2 Controllable disconnector (2)
IEC 61850 name
SA name
Description
Values
CTRL.DCCILO2
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
.ItlByPss.stVal
ITL_BYPASS
Interlocking bypass
1=Bypassed
CTRL.DCCSWI2
.Pos.stSeld
SELECTED
CB selected
1=Selected
CTRL.DCXSWI2
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
2.3.2.4
CTRL.Exxxxx1 Controllable earth switch (1)
Table 9:
CTRL.Exxxxx1 Controllable earth switch (1)
IEC 61850 name
SA name
Description
Values
CTRL.ESCILO1
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
.ItlByPss.stVal
ITL_BYPASS
Interlocking bypass
1=Bypassed
CTRL.ESCSWI1
.Pos.stSeld
SELECTED
CB selected
1=Selected
CTRL.ESXSWI1
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
2.3.3
Sensors and monitoring functions
2.3.3.1
LD0.SSCBR1 Circuit-breaker condition monitoring
Table 10:
LD0.SSCBR1 Circuit-breaker condition monitoring
IEC 61850 name
SA name
Description
Values
.APwrAlm.stVal
IPOW_ALM
Iyt alarm
1=Alarm
.APwrLO.stVal
IPOW_LO
Iyt lockout
1=Lockout
.CBLifAlm.stVal
CB_LIFE_ALM
CB lifetime alarm
1=Alarm
.ClsAlm.stVal
TRV_T_CL_ALM
Cls travel time alarm
1=Alarm
.LonTmAlm.stVal
MON_ALM
CB inactive alarm
1=Alarm
.OpnAlm.stVal
TRV_T_OP_ALM
Cls travel time alarm
1=Alarm
Table continues on next page
1MRS756879 D
Section 2
DNP3 data mappings
RED615
15
Point List Manual