IEC 61850 name
SA name
Description
Values
.SPCSO1.stVal
-
X130-Output 1
1/0=ON/OFF
.SPCSO2.stVal
-
X130-Output 2
1/0=ON/OFF
.SPCSO3.stVal
-
X130-Output 3
1/0=ON/OFF
2.4
Binary outputs
Table 59:
Explanations of the binary output table columns
Column name
Description
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name
The signal may have a defined label that is visible for example in ACT.
Description
Short description of the signal. See the application function block documentation
for more details.
Type
Output type. Some outputs can only be controlled with value “On”. Writing “Off” to
these points does not affect the function of the output. See DNP3 control relay
output block parameters.
2.4.1
System functions
2.4.1.1
LD0.LLN0/LPHD1 Reset indications and LEDs, reset device
Table 60:
LD0.LLN0/LPHD1 Reset indications and LEDs, reset device
IEC 61850 name
SA name
Description
Type
LD0.LLN0
.LEDRs1.Oper.ctlVal
-
Reset indications and LEDs
On
.LEDRs2.Oper.ctlVal
-
Reset alarm LEDs
On
LD0.LPHD1
.RsDev.Oper.ctlVal
-
Reset device
On
2.4.1.2
LD0.DNPGGIO1 Parameter setting group control
Table 61:
LD0.DNPGGIO1 Parameter setting group control
IEC 61850 name
SA name
Description
Type
LD0.DNPGGIO1
.ActSG1.ctlVal
-
Setting group 1
On
.ActSG2.ctlVal
-
Setting group 2
On
.ActSG3.ctlVal
-
Setting group 3
On
.ActSG4.ctlVal
-
Setting group 4
On
.ActSG5.ctlVal
-
Setting group 5
On
.ActSG6.ctlVal
-
Setting group 6
On
Section 2
1MRS756879 D
DNP3 data mappings
28
RED615
Point List Manual