0xA
CS
IEC 61850 name
SA name
Description
Values
2068
2.08
.MemClr.Oper.ctlVal
Clear DR memory
1=Clear
LD0.RESVMMXU1
2074
2.14
.RcdRs.Oper.ctlVal
Reset Uo (1) max demands
1=Reset
2.5.2
CTRL.CBCSWI1 Circuit breaker control (1)
Table 83:
CTRL.CBCSWI1 Circuit breaker control (1)
0xA
CS
IEC 61850 name
SA name
Description
Values
CTRL.CBCSWI1
2048
1.00
.Pos.Oper.ctlVal
Select open
1=Select
2049
1.01
.Pos.Oper.ctlVal
Select close
1=Select
2050
1.02
.Pos.Oper.ctlVal
Cancel selection
1=Cancel
2051
1.03
.Pos.Oper.ctlVal
Execute selection
1=Execute
2052
1.04
.Pos.Oper.ctlVal
Direct open
1=Open
2053
1.05
.Pos.Oper.ctlVal
Direct close
1=Close
2.5.3
LD0.LDEV1 Protection relay's warm reset (1)
Table 84:
LD0.LDEV1 Protection relay's warm reset (1)
0xA
CS
IEC 61850 name
SA name
Description
Values
LD0.LDEV1
2080
3.00
.WrmStrCmd.Oper.ctlVal
Warm reboot of protection relay 1=Reboot
2.5.4
Unmapped control points
Table 85:
Unmapped control points
IEC 61850 name
Description
Value
LD0.LLN0
.MeasStatRs.Oper.ctlVal
Reset all min. and max. demands
1=Reset
LD0.FLTRFRC1
.RcdRs.Oper.ctlVal
Reset fault record data
1=Reset
1MRS758336 B
Section 2
Modbus data mappings
REU611
51
Point List Manual