RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
9270
u16
1
Data object ID1
1)
9271
u16
1
Data object ID2
1)
9272
u16
1
Event data value 1
1)
9273
u16
1
Event data value 2
1)
Record 3 data to read:
If selected
9274
u16
1
- Record sequence num
1...500
9275
u16
1
- Unread records left
0...499
Timestamp of record
9276
u16
1
- Year, Month
Year/Month
9277
u16
1
- Day, Hour
Day/Hour
9278
u16
1
- Minute, Second
Min/Sec
9279
u16
1
- Millisecond
Millisecond
9280
u16
1
Event identification
1)
9281
u16
1
Data object ID1
1)
9282
u16
1
Data object ID2
1)
9283
u16
1
Event data value 1
1)
9284
u16
1
Event data value 2
1)
Record 4 data to read:
If selected
9285
u16
1
- Record sequence num
1...500
9286
u16
1
- Unread records left
0...499
Timestamp of record
9287
u16
1
- Year, Month
Year/Month
9288
u16
1
- Day, Hour
Day/Hour
9289
u16
1
- Minute, Second
Min/Sec
9290
u16
1
- Millisecond
Millisecond
9291
u16
1
Event identification
1)
9292
u16
1
Data object ID1
1)
9293
u16
1
Data object ID2
1)
9294
u16
1
Event data value 1
1)
9295
u16
1
Event data value 2
1)
Record 5 data to read:
If selected
9296
u16
1
- Record sequence num
1...500
9297
u16
1
- Unread records left
0...499
Timestamp of record
9298
u16
1
- Year, Month
Year/Month
Table continues on next page
1MRS758336 B
Section 2
Modbus data mappings
REU611
33