2.3.1.2
CTRL.CBCILO1 Circuit breaker enable signals (1)
Table 5:
CTRL.CBCILO1 Circuit breaker enable signals (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.CBCILO1
2824
176.08
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
2825
176.09
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
2.3.1.3
CTRL.CBCSWI1 Circuit breaker (1) mom. position
Table 6:
CTRL.CBCSWI1 Circuit breaker (1) mom. position
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.CBCSWI1
POSITION
2804
175.00
.Pos.stVal
-
Close bit
1=Close
2805
175.01
.Pos.stVal
-
Open bit
1=Open
2806
175.02
.Pos.stVal
-
Fault bit
1=Pos(00/11)
2.3.1.4
CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
Table 7:
CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.CBCSWI1
POSITION
2816
176.00
.Pos.stVal
Close bit
1=Close
2817
176.01
.mcd
2818
176.02
.Pos.stVal
Open bit
1=Open
2819
176.03
.mcd
2820
176.04
< reserved >
2821
176.05
< reserved >
2822
176.06
.Pos.stSeld
SELECTED
CB selected for control
1=Selected
2823
176.07
.mcd
2826
176.10
.SynItlByps.stVal
ITL_BYPASS
Interlock bypass
1=Bypass
2827
176.11
.mcd
1MRS758336 B
Section 2
Modbus data mappings
REU611
13
Point List Manual