SEMOD175210-2 v7
Table 51. Loss of voltage check LOVPTUV
Function
Range or value
Accuracy
Operate voltage
(0–100)% of UBase
±0.5% of U
r
Reset ratio
<105%
-
Pulse timer when disconnecting all three
phases
(0.050–60.000) s
±0.5% ±25 ms
Timers
(0.000–60.000) s
±0.5% ±25 ms
Line distance protection REL650
1MRK 506 384-BEN H
Version 2.2
Hitachi Power Grids
71