45
Checking the self supervision signals
&KDSWHU
(QHUJLVLQJWKHWHUPLQDO
ADC-module = OK
No problem detected.
None.
ADC-module = Fail
The A/D conversion
module has failed.
Contact your ABB representative for ser-
vice.
Slot04BIM1 = Fail
(Example data, see
following section for
details)
I/O module has failed.
Check that the I/O module has been config-
ured and connected to the IOP1- block.
If the problem persists, contact your ABB
representative for service.
RealTimeClock = OK
No problem detected.
None.
RealTimeClock =
Warning
The real time clock has
been reset.
Set the clock.
TimeSync = OK
No problem detected.
None.
TimeSync = Warning
No time synchroniza-
tion.
Check the synchronization source for prob-
lems.
If the problem persists, contact your ABB
representative for service.
,QGLFDWHGUHVXOW
3RVVLEOHUHDVRQ
3URSRVHGDFWLRQ