1MRS 750616-MUM
Directional or Non-Directional Earth-Fault Relay
Technical Reference Manual
REJ 527
59
4.2.2.
Serial communication connections
The REJ 527 is interfaced with a fibre-optic bus by means of the bus connection
module RER 103 via the D9S-type connector X2 located on the rear panel of the
device. The terminals of the fibre-optic cables are connected to the counter terminals
Rx (Receiver) and Tx (Transmitter) of the bus connection module. The fibre-optic
cables are linked from one protection relay to another and to the substation level
communication unit, e.g. SRIO 1000M and the RER 125.
The optical PC-connection on the front panel of the relay is used to connect the relay
to a fibre-optic SPA bus via opto-cable 1MKC950001-1.
Table 4.2.1-3
Output contacts
Terminal
Function
X2.1-3
PO1, closing contact
X2.1-4
X2.1-5
PO2, closing contact
X2.1-6
X2.1-7
SO1, common
X2.1-8
SO1, NC
X2.1-9
SO1, NO
X2.1-10
SO2, common
X2.1-11
SO2, NC
X2.1-12
SO2, NO
Table 4.2.1-4
Internal Relay Fault (IRF) contact
Terminal
Function
X2.1-13
Internal relay fault, common
X2.1-14
Closed; IRF, or U
aux
disconnected
X2.1-15
Closed; no IRF, and U
aux
connected
Table 4.2.1-5
Binary input
Terminal
Function
X2.1-17
Input+
X2.1-18
Input-
Table 4.2.2-1
RS-485 connector X2 for the RER 103
Terminal
Function
X.2.2-1
Data A (data )
X.2.2-2
Data B (data signal -)
X.2.2-3
RTS A (request to send +)
X.2.2-4
RTS B (request to send -)
X.2.2-5
COL A (2.8 V on relay)
X.2.2-6
COL B (2.2 V on relay)
X.2.2-7
GND
X.2.2-8
NC
X.2.2-9
+5 Vdc, auxiliary voltage (max. 200 mA)
Summary of Contents for REJ 527
Page 1: ...REJ 527 Directional or Non Directional Earth Fault Relay Technical Reference Manual ...
Page 2: ......
Page 74: ......
Page 75: ......