1MRS 750616-MUM
Directional or Non-Directional Earth-Fault Relay
Technical Reference Manual
REJ 527
31
SGF1...SGF5
Switchgroups SGF1...SGF5 are used for configuring the desired function as follows.
Table 4.1.4.6-2
SGF1
Switch
Function
Default
setting
SGF1/1
Selection of the latching feature for power output PO1
0
SGF1/2
Selection of the latching feature for power output PO2
0
• When the switch is in position 0 and the measuring signal which
caused the trip falls below the set start value, the output contact
will return to its initial state.
• When the switch is in position 1, the output contact will remain
active although the measuring signal which caused the trip falls
below the set start value.
A latched output contact can be unlatched either via the HMI, the
external binary input or the serial bus.
SGF1/3
Minimum pulse length for signal outputs SO1 and SO2
• 0=80 ms
• 1=40 ms
0
SGF1/4
Minimum pulse length for power outputs PO1 and PO2
• 0=80 ms
• 1=40 ms
Note!
The latching function of PO1 and PO2 will overrun this function.
0
SGF1/5
CBFP
• When the switch is in position 0, the CBFP is not in use.
• When the switch is in position 1, the signal to output PO1 will
start a timer which will generate a delayed signal to output PO2,
provided that the fault is not cleared before the CBFP operate
time has elapsed.
0
SGF1/6
Not in use
0
SGF1/7
Not in use
0
SGF1/8
Not in use
0
Σ
SGF1
0