Table 72. Voltage-restrained time overcurrent protection VRPVOC
Function
Range or value
Accuracy
Start overcurrent
(2.0 - 5000.0)% of IBase
±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
Reset ratio, overcurrent
> 95%
-
Operate time, start overcurrent at 0 to 2 x I
set
Min. = 15 ms
-
Max. = 30 ms
Reset time, start overcurrent at 2 to 0 x I
set
Min. = 15 ms
-
Max. = 30 ms
Operate time, start overcurrent at 0 to 10 x I
set
Min. = 5 ms
Max. = 20 ms
-
Reset time, start overcurrent at 10 to 0 x I
set
Min. = 20 ms
Max. = 35 ms
-
Independent time delay to operate at 0 to 2 x I
set
(0.00 - 6000.00) s
±0.2% or ±35 ms whichever is
greater
Inverse time characteristics,
see tables
13 curve types
Minimum operate time for inverse time characteristics
(0.00 - 60.00) s
±0.2% or ±35 ms whichever is
greater
High voltage limit, voltage dependent operation
(30.0 - 100.0)% of UBase
±1.0% of U
r
Start undervoltage
(2.0 - 100.0)% of UBase
±0.5% of U
r
Reset ratio, undervoltage
< 105%
-
Operate time start undervoltage at 2 to 0 x U
set
Min. = 15 ms
-
Max. = 30 ms
Reset time start undervoltage at 0 to 2 x U
set
Min. = 15 ms
-
Max. = 30 ms
Independent time delay to operate, undervoltage at 2 to 0 x U
set
(0.00 - 6000.00) s
±0.2% or ±35 ms whichever is
greater
Internal low voltage blocking
(0.0 - 5.0)% of UBase
±0.25% of U
r
Overcurrent:
Critical impulse time
Impulse margin time
10 ms typically at 0 to 2 x I
set
15 ms typically
-
Undervoltage:
Critical impulse time
Impulse margin time
10ms typically at 2 to 0 x U
set
15 ms typically
-
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1