The limit counter provides four independent limits to be checked against the
accumulated counted value. The four limit reach indication outputs can be utilized
to initiate proceeding actions. The output indicators remain high until the reset of
the function.
It is also possible to initiate the counter from a non-zero value by resetting the
function to the wanted initial value provided as a setting.
If applicable, the counter can be set to stop or rollover to zero and continue
counting after reaching the maximum count value. The steady overflow output flag
indicates the next count after reaching the maximum count value. It is also possible
to set the counter to rollover and indicate the overflow as a pulse, which lasts up to
the first count after rolling over to zero. In this case, periodic pulses will be
generated at multiple overflow of the function.
15.9.3
Setting guidelines
GUID-5AECCDBC-7385-4D9F-940C-9D4A0E59B106 v1
GUID-DA5DA8D7-4821-4BFB-86CC-28658E376270 v2
The parameters for Limit counter L4UFCNT are set via the local HMI or PCM600.
15.10
Running hour-meter TEILGAPC
15.10.1
Identification
GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Running hour-meter
TEILGAPC
-
-
15.10.2
Application
GUID-225D8341-2D31-49F1-9B49-571346C0FE26 v1
The function is used for user-defined logics and it can also be used for different
purposes internally in the IED. An application example is to accumulate the total
running/energized time of the generator, transformer, reactor, capacitor bank or
even line.
Settable time limits for warning and alarm are provided. The time limit for
overflow indication is fixed to 99999.9 hours. At overflow the accumulated time
resets and the accumulation starts from zero again.
15.10.3
Setting guidelines
GUID-D3BED56A-BA80-486F-B2A8-E47F7AC63468 v1
The settings
tAlarm
and
tWarning
are user settable limits defined in hours. The
achievable resolution of the settings is 0.1 hours (6 minutes).
Section 15
1MRK 505 393-UEN B
Monitoring
348
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...