Figure 92:
Earth fault in Non-effectively earthed systems
9.3.3.5
Direct earthed system
GUID-EA622F55-7978-4D1C-9AF7-2BAB5628070A v8
In direct earthed systems, an earth fault on one phase is indicated by voltage
collapse in that phase. The other healthy phase will still have normal phase-to-earth
voltage. The residual sum will have the same value as the remaining phase-to-earth
voltage, which is shown in Figure
UL
1
IEC07000189-2-en.vsd
IEC07000189 V2 EN-US
Figure 93:
Earth fault in Direct earthed system
1MRK 505 393-UEN B
Section 9
Voltage protection
Line differential protection RED650 2.2 IEC
199
Application manual