15.2.2
Application
Use a common global source for example GPS time synchronization inside each
substation as well as inside the area of the utility responsibility to achieve a common time
base for the IEDs in a protection and control system. This makes comparison and analysis
of events and disturbance data between all IEDs in the power system possible.
Time-tagging of internal events and disturbances are an excellent help when evaluating
faults. Without time synchronization, only the events within the IED can be compared to
one another. With time synchronization, events and disturbances within the entire station,
and even between line ends, can be compared during evaluation.
In the IED, the internal time can be synchronized from a number of sources:
•
SNTP
•
IRIG-B
•
DNP
•
IEC60870-5-103
Micro SCADA OPC server should not be used as a time synchronization
source.
15.2.3
Setting guidelines
System time
The time is only possible to set inside the IED via the local HMI by navigating to
Configuration/Time/SYSTEMTIME
with year, month, day, hour, minute and second.
Synchronization
With external time synchronization the setting how to synchronize for the real-time clock
(TIME) are set via local HMI or PCM600.
TimeSynch
The setting
TIMESYNCGEN
is used to set the source of the time synchronization. The
setting alternatives are:
CoarseSyncSrc
which can have the following values:
•
Disabled
•
SNTP
•
DNP
•
IEC60870-5-103
1MRK 511 286-UUS A
Section 15
Basic IED functions
327
Application manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Page 2: ......
Page 26: ...20...
Page 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Page 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Page 82: ...76...
Page 92: ...86...
Page 170: ...164...
Page 176: ...170...
Page 274: ...268...
Page 288: ...282...
Page 350: ...344...
Page 369: ...363...