During the
tIntermediate
time the position indication is allowed to be in an intermediate
(00) state. When the time has expired, the switch function is reset. The indication of the
mid-position at SCSWI is suppressed during this time period when the position changes
from open to close or vice-versa.
If the parameter
AdaptivePulse
is set to
Adaptive
the command output pulse resets when
a new correct end position is reached. If the parameter is set to
Not adaptive
the command
output pulse remains active until the timer
tOpenPulsetClosePulse
has elapsed.
tOpenPulse
is the output pulse length for an open command. The default length is set to
200 ms for a circuit breaker (SXCBR) and 200 ms for a disconnector or grounding switch
(SXSWI).
tClosePulse
is the output pulse length for a close command. The default length is set to 200
ms for a circuit breaker (SXCBR) and 200 ms for a disconnector or grounding switch
(SXSWI).
SuppressMidPos
when
Enabled
will suppress the mid-position during the time
tIntermediate
.
SwitchType
is an enumeration according to IEC 61850-7-4 to indicate the switch type
assigned to SXSWI
10.3.4.3
Bay control (QCBAY)
If the parameter
AllPSTOValid
is set to
No priority
, all originators from local and remote
are accepted without any priority.
10.4
Interlocking
10.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logical node for interlocking
SCILO
-
3
Interlocking for busbar grounding switch BB_ES
-
3
Interlocking for bus-section breaker
A1A2_BS
-
3
Interlocking for bus-section
disconnector
A1A2_DC
-
3
Interlocking for bus-coupler bay
ABC_BC
-
3
Interlocking for 1 1/2 breaker diameter
BH_CONN
-
3
Interlocking for 1 1/2 breaker diameter
BH_LINE_A
-
3
Table continues on next page
Section 10
1MRK 511 286-UUS A
Control
224
Application manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Page 2: ......
Page 26: ...20...
Page 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Page 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Page 82: ...76...
Page 92: ...86...
Page 170: ...164...
Page 176: ...170...
Page 274: ...268...
Page 288: ...282...
Page 350: ...344...
Page 369: ...363...