6.1.4.5
Alarm level operation
M16850-196 v6
The 1Ph High impedance differential protection HZPDIF function has a separate
alarm level, which can be used to give alarm for problems with an involved current
transformer circuit. The setting level is normally selected to be around 10% of the
operating voltage
U>Trip
.
As seen in the setting examples above the sensitivity of HZPDIF function is
normally high, which means that the function will in many cases operate also for
short circuits or open current transformer secondary circuits. However the
stabilizing resistor can be selected to achieve sensitivity higher than normal load
current and/or separate criteria can be added to the operation, like a check zone.
This can be either another IED, with the same HZPDIF function, or be a check
about the fault condition, which is performed by an earth overcurrent function or
neutral point voltage function.
For such cases where operation is not expected during normal service the alarm
output should be used to activate an external shorting of the differential circuit
avoiding continuous high voltage in the circuit. A time delay of a few seconds is
used before the shorting and alarm are activated. Auxiliary relays with contacts that
can withstand high voltage shall be used, like RXMVB types.
The metrosil operating characteristic is given in the following figure.
IEC05000749 V1 EN-US
Figure 37:
Current voltage characteristics for the non-linear resistors, in the range 10-200 V, the average
range of current is: 0.01–10 mA
1MRK 505 388-UEN B
Section 6
Differential protection
Busbar protection REB650 2.2 IEC
89
Application manual
Summary of Contents for REB650
Page 1: ...RELION 650 SERIES Busbar protection REB650 Version 2 2 Application manual...
Page 2: ......
Page 18: ...12...
Page 28: ...22...
Page 38: ...32...
Page 78: ...72...
Page 96: ...90...
Page 136: ...130...
Page 150: ...144...
Page 156: ...150...
Page 232: ...226...
Page 278: ...272...
Page 298: ...292...
Page 310: ...304...
Page 320: ...314...
Page 321: ...315...