Off
•
SPA
•
LON
•
DNP
•
IEC 60870-5-103
The function input to be used for minute-pulse synchronization is called
BININPUT. For a description of the BININPUT settings, see the
Technical
Manual
.
The system time can be set manually, either via the local HMI or via any of the
communication ports. The time synchronization fine tunes the clock (seconds and
milliseconds).
The parameter
SyncMaster
defines if the IED is a master, or not a master for time
synchronization within a Substation Automation System, for IEDs connected in a
communication network (IEC 61850-8-1). The
SyncMaster
can have the following
values:
•
Off
•
SNTP -Server
IEEE 1588 (PTP)
GUID-424227EC-74A1-4628-8948-C1876840ABFE v3
Precision Time Protocol (PTP) is enabled/disabled using the Ethernet configuration
tool /ECT) in PCM600.
PTP
can be set to
On
,
Off
or
Slave only
. When set to
Slave only
the IED is
connected to the PTP-group and will synchronize to the grandmaster but cannot
function as the grandmaster.
A PTP-group is set up by connecting the IEDs to a network and enabling PTP. To
set one IED as the grandmaster change Priority2 to 127 instead of the default 128.
IEC16000089-1-en.vsdx
IEC16000089 V1 EN-US
Figure 101:
Enabling PTP in ECT
The
PTP VLAN
tag must have the same value in station clock and in the IED. The
default value is set to 0.
The
PTP VLAN
tag does not need to be the same on all access points in one IED. It
is possible to mix as long as they are the same for all devices on each subnet.
1MRK 505 388-UEN B
Section 17
Basic IED functions
Busbar protection REB650 2.2 IEC
289
Application manual
Summary of Contents for REB650
Page 1: ...RELION 650 SERIES Busbar protection REB650 Version 2 2 Application manual...
Page 2: ......
Page 18: ...12...
Page 28: ...22...
Page 38: ...32...
Page 78: ...72...
Page 96: ...90...
Page 136: ...130...
Page 150: ...144...
Page 156: ...150...
Page 232: ...226...
Page 278: ...272...
Page 298: ...292...
Page 310: ...304...
Page 320: ...314...
Page 321: ...315...