Sets the logic state of digital output X113:7.
Active high
DO X113:7 logic
state
SAFEIO.71
Active high
: The digital output is on when
the indicated signal is active.
For the Q950, ABB has configured
the POUS indication signal to this digital
output at the factory.
Note:
The following indications are generated when POUS is activated:
AA97 FSO POUS
request warning
and
7A97 FSO premature POUS fault
. These are not user-configurable.
■
Inverter unit parameter settings
The parameter setting in ACS880 primary control program:
Description
Default value
Name
No.
Selects which indications are given when one or both Safe
torque off (STO) signals are switched off or lost.
Warning/Warning
STO indication
run/stop
31.22
Warning/Warning
is the recommended setting.
We recommend that you do not set parameter
31.22 STO indication run/stop
to value
0
,
1
or
2
. This prevents the inverter units from generating a fault every time the FSO module
activates the inverter unit STO function.
For more information, see the firmware manual.