The following describes the configuration parameters which may be Enabled/Disabled and configured
by the user. Refer to Appendix D for the ranges of values the parameters may take and their factory
default settings.
Temperature Alarms
The Pulsar Edge has several alarm thresholds that can be set based on temperature.
•
High Temperature Alarm:
The High Battery Thermal Alarm Threshold (thr) is the monitored battery temperature at
which above this threshold results in a High Battery Thermal alarm. This alarm threshold can be set from 30°C to
85°C and its severity is configurable. The alarm retires when the temperature drops to 10°C below the set
threshold. The factory default setting is 55°C with Power Minor severity.
•
Very High Temperature Alarm:
The Very High Battery Thermal Alarm Threshold is a second alarm threshold
available for high battery temperature. The monitored battery temperature at which above this threshold results in
a Very High Battery Thermal alarm. This alarm threshold can be set from 30°C to 85°C and its severity is
configurable. The alarm retires when the temperature drops to 10°C below the set threshold. The factory default
setting is TBD°C with Power Major severity.
•
Low Temperature Alarm:
The Low Battery Thermal Alarm Threshold is the monitored battery temperature at which
below this threshold results in a Low Battery Thermal alarm. This alarm threshold can be set from
-
40°C to 10°C and
its severity is configurable. The alarm retires when the temperature raises 10°C above the set threshold. The factory
default setting is TBD°C with Power Minor severity.
•
Very Low Temperature Alarm:
The Very Low Battery Thermal Alarm Threshold is a second alarm threshold available
for low battery temperature. The monitored battery temperature at which below this threshold will result in a Very Low
Battery Thermal alarm. This alarm threshold can be set from 40°C to 10°C and its severity is configurable. The alarm
retires when the temperature raises 10°C above the set threshold. The factory default setting is TBD°C with Power Major
severity.
Figure 26 Slope Thermal Compensation
Summary of Contents for Pulsar Edge
Page 2: ...Page 2 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 6: ...Page 6 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 14: ...Page 14 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 22: ...Page 22 Copyright 2021 ABB All rights reserved Step Action o o hadtobeperformed location ...
Page 34: ...Page 34 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 41: ...Page 41 Copyright 2021 ABB All rights reserved Figure 9 Pulsar Edge Status Menu ...
Page 49: ...Page 49 Copyright 2021 ABB All rights reserved Figure 13 Reports Menu ...
Page 50: ...Page 50 Copyright 2021 ABB All rights reserved Figure 14 Maintenance Menu ...
Page 51: ...Page 51 Copyright 2021 ABB All rights reserved Figure 15 Settings Menu ...
Page 92: ...Page 92 Copyright 2021 ABB All rights reserved o o o o ...
Page 108: ...Page 108 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 116: ...Page 116 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 154: ...Page 154 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 162: ...Page 162 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 192: ...Page 192 Copyright 2021 ABB All rights reserved This page intentionally left blank ...