14 OI/FEP610/FEH610-EN Rev. B |
ProcessMaster FEP610, HygienicMaster FEH610
5.1.4
Devices with a wafer-type design
Fig. 10: Installation set for wafer-type installation (example)
1
Threaded rod
2
Nut with washer
3
Centering sleeves
For devices with a wafer-type design, ABB offers an
installation set as an accessory that comprises threaded rods,
nuts, washers and centering sleeves for installation.
5.1.5
Flow direction
Fig. 11: Flow direction
The device measures the flowrate in both directions. Forward
flow is the factory setting, as shown in Fig. 11.
5.1.6
Elektrode axis
Fig. 12: Orientation of the electrode axis
1
Elektrode axis
The electrode axis should be horizontal if at all possible or no
more than 45° from horizontal.
5.1.7
Mounting position
Fig. 13: Mounting position
A
Vertical installation for measuring abrasive fluids,
preferably with flow in upward direction.
B
In case of horizontal installation, the Meter tube must
always be completely full.
Provide for a slight incline of the connection for degassing.
NOTE
Prefer vertical installation in hygienic applications!
With horizontal installation assure the sensor is self-
drainable.
G12060
1
2
3
3
G12006
G12007
≤ 45°
1
G12009
A
B
3°