![ABB ProcessMaster FEM630 Instruction Manual Download Page 14](http://html1.mh-extra.com/html/abb/processmaster-fem630/processmaster-fem630_instruction-manual_3951466014.webp)
14
P R O C E S S M A S T E R
W A F E R
F E
M
6 3 0
| COM/FE
M
630/E/MB
-
EN RE
V. A
9 Menu Structure in HMI
Menu
Settings
Description
Communication
Ethernet
General
Base Protocol Stack
EtherNet/IP
Indicates the communication protocol for information purposes only
Internet layer
DHCP client
enabled, disabled
Factory default: enabled. If disabled, the host IP address defaults to 192.168.001.122
Host IP address
Allows for IP address setting 192.168.001.122 is the factory default in case DHCP client is
set to fixed IP
Subnet mask
255.255.255.000
factory default: 255.255.255.000
Gateway IP address
000.000.000.000
Factory default = 000.000.000.000
If it's part of the subnet, the first block of numbers should be identical to HOST IP - for
example, 192.168.1.10
NTPServer1 IP address
factory default: 000.000.000.000
NTPServer2 IP address
factory default: 000.000.000.000
Host name
factory default: ABB-Flow
Domain name
factory default: my-domain
DNS1 IP address
automatically set with DHCP = ON: 000.000.000.000
DNS2 IP address
Webserver
Access
"disabled, Read only,
Full"
factory default: Full
Reset credentials
Allows for resetting the webserver password
Session timeout
5 min
Timeout time closing the webserver session.
Default value: 5 minutes
Possible settings: Min: 1 Max: 4294967000
EthernetIP
Access
disabled, Read only, Full
Factory Default is
disabled
Set to
Full
or
Read Only
with Omron or Rockwell PLCs
Device status
Mod
<G>
Net
<G>
P1
P1 = Port 1 of the Ethernet card
Mod = Module Status
Mod showing
<G>
continously = Device ready for Operation. Working properly
Mod changing between
<G>
and
< >
= Standby. Device not configured yet
Mod changing between
<R>
and
< >
= Simple error which can be fixed
Mod showing
<R>
continously = Major Error. Non removable serious error
Mod showing
< >
continously = No Power
Net = Network Status
Net showing
<G>
continously = Connected. Device has at least one established
connection
Net changing between
<G>
and
< >
= No Connection. Device did not establish any
connections, but was assigned an IP address
Net showing
<R>
continously = Dublicated IP address. Device has detected that the
device IP address is already in use
Net showing
< >
continously = No supply voltage or IP Address.
Net changing between
<R>
and
< >
= Connection timeout
Vendor ID
46
Product / Device
Type
43
Product name
EMF FEW5/FEP_FEH6
Product code
5002
Product major rev.
1
Product minor rev.
1