18/40 - 647008/002 - 2000/05 it-en
C.S. 40 A
1
1.25
1.5
1.75
0.1
0.2
0.5
2
3
4
8
0
0
0
0
0
0
0.1
OFF
0
0
0
I>> / In
t>>
I>>>/In
OFF
OFF
6.2.1.2.3. Example of setting
An example of setting the protection against selective short-
circuit I>> (50) is now given.
A protection with the following characteristics is to be made:
• The above-mentioned circuit-breaker has 40 A C.S. mounted
(In = 40 A).
• Threshold I>> = 110 A
• Trip time t>> = 0.2 s.
And therefore you must:
• Calculate the relationship I>>/In: 110 A/40 A = 2.75.
• Set the relative dip switches to obtain a sum of 2.75 (fig. 1
ref. L).
• Set the dip switches relative to the time t>> to obtain 0.2 s (fig.
1 ref. I)
The configuration shown in the figure carries out the required
setting:
6.2.1.2.3. Esempio di impostazione
Si riporta ora un esempio di impostazione della protezione di
cortocircuito selettiva I>> (50).
Si vuole realizzare una protezione con le seguenti caratteristi-
che:
• L’interruttore in oggetto monta C.S. da 40 A (In= 40 A).
• Soglia I>> = 110 A.
• Tempo di intervento t>> = 0,2 s.
E quindi si deve:
• Calcolare il rapporto I>>/In: 110 A/40 A = 2,75.
• Predisporre i dip switch relativi in modo da ottenere una
somma di 2,75 (fig. 1 rif. L).
• Predisporre i dip switch relativi al tempo t>> in modo da
ottenere 0,2 s (fig. 1 rif. I).
La configurazione riportata nella figura realizza l’impostazione
richiesta: