29
USER M A N UA L
11: External battery AH
Interface
Settings
Parameter 1:
Set up external battery AH value of the UPS. (unit: AH)
7-999:
setting the external battery capacity from 7 to 999. Please set up this figure if
external battery modules are connected. (Default: 20Ah)
12: External battery module numbers
Interface
Settings
Parameter 1:
Set connected external battery module numbers. The setting range is
from 0 to 9. (Default: 0)
13: Input dry contact
Interface
Settings
Parameter 1:
Set input dry contact.
DIS:
Disable the function (Default)
TON:
UPS Turn On.
TOF:
UPS Turn Off.
MBS:
Maintain Bypass.
14: Output dry contact
Interface
Settings
Parameter 1:
Set output dry contact.
SAL:
Summary alarm (Default)
BTA:
Battery active
LBA:
Low battery
UPN:
UPS normal
BSA:
Bypass active
15: EPO
Interface
Settings
Parameter 1:
Clear EPO warning.
EPO active, the UPS output is cut-off. To recover the normal status, EPO connector
must first be closed. Enter this menu to clear the status of EPO. The UPS will stop
alarming and will recover in Bypass-mode. Note that the UPS needs be turned on by
manual operation.