QUICK START GUIDE

 

Page 6

 

© 2021 ABB. All rights reserved.

 

 

 

Specifications and Application

• 

 

• 

External Surge Protective Device (SPD) is required on all AC inputs.

 

• 

Equipment and subassembly ports: 

 

1.

 

are suitable for connection to intra

-

building or unexposed wiring or cabling;

 

2.

 

can be connected to shielded intra

-

building cabling grounded at both ends.

 

• 

Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an Integrated 

Ground Plane (Mesh Bonding Network or Common Bonding Network).

 

Installation Environment 

-

 Install in Network Telecommunication Facilities, OSP, or where NEC applies.

• 

Battery return may be either Isolated DC return (DC

-

I) or Common DC return (DC

-

C).

 

Reference Documents

 

These documents are available at 

 

 

 

Safety Statements

 

• 

Do not install this equipment over combustible surfaces.

 

• 

Rules and Regulations 

-

 Follow all national and local rules and regulations when making field connections.

 

• 

Compression Connectors

 

• 

U. S. or Canada installations 

-

 use Listed/Certified compression connectors to terminate Listed/Certified field

-

wire 

conductors where required.

 

• 

All  installations 

-

  apply  the  appropriate  connector  to  the  correct  size  conductor  as  specified  by  the  connector 

manufacturer, using only the connector manufacturer

s recommended or approved tooling for that connector.

 

• 

Electrical Connection Securing: Torque to the values specified on labels or in the product documentation.

 

• 

Cable Dress 

-

 dress to avoid damage to the conductors and undue stress on the connectors.

 

• 

Fuses and Circuit Breakers 

-

 Size as required by the National Electric Code (NEC) and/or local codes.

 

• 

Refer to the equipment ratings to assure current does not exceed:

 

• 

Continuous Load (List 1) 

-

 60% of protector rating

 

• 

Maximum Load (List 2 

-

 typically end of discharge) 

-

 80% of protector rating.

 

• 

Field

-

wired Conductors 

-

 Follow all National Electric Code (NEC) and local rules and regulations .

 

• 

Insulation rating: 90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.

 

• 

Size AC field

-

wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board circuit breaker 

rating.

 

• 

Size DC field

-

wired conductors with 90°C ampacity (NEC) equal to or greater than circuit breaker/fuse rating.

 

• 

AC and DC input disconnect/protection 

-

 Provide accessible devices to remove input power in an emergency.

 

• 

Alarm Signals 

-

 Provide external current limiting protection. Rating 60V, 0.5A unless otherwise noted.

 

• 

Grounding 

-

 Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the cabinet ac 

service ground bus. In huts, vaults, and central offices connect to the system bonding network.

 

• 

Circuit Breakers and Fuses 

-

 Use only those specified in the equipment ordering guide.

 

• 

GMT Style Fuses 

-

 Use only fuses provided with safety caps.

 

Summary of Contents for Power Express

Page 1: ...cure lug with screws 10 32 provided Typical self Sockets 5 16 7 16 and 1 2 Wire cutters and strippers DC Output Terminals Alarm Chassis Ground I50028529 Shelf only Alarm Connector Chassis Ground All shelves DC Output Return Terminals Ground Typical Shelf 150028529 Shelf 48Vinput and output unregulated 150036912 Shelf 48Vinput 57V output regulated Jl 1111 11111 1 0 0 Read and follow all safety stat...

Page 2: ...nce option see note below B5 Remove POS Lug Bridging Bus B6 Connect DC Input feed return to POSA lug landing B7 Connect Output Reference ground to POSB lug landing Without Remote Output Reference option B8 Connect to NEGA or NEGB lug landing 1 cable Torque All Lug Nuts B9 Torque all lug nuts to 65 in lb 7 3Nm 7 16 socket Notes Apply these options only when directed by the site engineering instruct...

Page 3: ... downward angle Pull the wire out of the terminal Wire Entry 24 8 gage 150036912 Negative 48V Positive ground 150028529 Step 5 Connect DC Outputs Connect DC Output and DC Output Return wires for each output 32 DC Outputs 8 per Module Step 6 Connect Alarm Cable 1 Remove alarm connector from the chassis 2 Connect alarm cable 3 Insert alarm connector into the chassis 1 Strip wire 3 16 2 Insert wire f...

Page 4: ...s with loads are turned ON circuits without loads are turned OFF Information LEDs and Alarm Latch Condition Shelf LED Shelf Alarm OK ALM Class 2 Circuit ON G OFF Class 2 Circuit OFF G OFF Class 2 Circuit Over Current Shorted OFF Y Alarm Class 2 Circuit Fail 1 or more OFF R Alarm Input Voltage Very Low OFF OFF Alarm Input Voltage Out of Range OFF Y BLINK Alarm Reversed Input Polarity OFF R BLINK Y ...

Page 5: ...Button to enter the manual mode hold until the OK LED turns OFF and back ON 2 seconds 1 Tap the Button repeatedly until the desired Circuit LED blinks 2 Press and hold the Button to toggle the circuit ON OFF hold until the OK LED turns OFF and back ON 2 seconds 3 Repeat from step 2 to operate another circuit 4 Automatic operation is restored after a few seconds of Button Inactivity The OK LED is t...

Page 6: ...ress dress to avoid damage to the conductors and undue stress on the connectors Fuses and Circuit Breakers Size as required by the National Electric Code NEC and or local codes Refer to the equipment ratings to assure current does not exceed Continuous Load List 1 60 of protector rating Maximum Load List 2 typically end of discharge 80 of protector rating Field wired Conductors Follow all National...

Page 7: ... with ringer modules hazardous voltages will be present on the ringer output connectors Use the following precautions in addition to proper job training and safety procedures Use only properly insulated tools Remove all metallic objects key chains glasses rings watches or other jewelry Follow Lock Out Tag Out LOTO procedures customer specified site specific or general as appropriate Disconnect all...

Page 8: ...ibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB Copyright 2021 ABB All rights reserved ABB 601 Shiloh Rd Plano ...

Reviews: