Chapter 3. Accessory Operation
The EntelliGuard® Control Unit activates the Bell Alarm with
Lockout for ground fault protection trips only.
The catalog numbers for the Bell Alarm with Lockout are listed
in Table 10. For installation instructions see GEH6278.
Catalog No.
Contact Rating
SPBAL240
6 A at 240 Vac
0.25 A at 250 Vdc
0.50 A at 125 Vdc
SPBAL600
6 A at 600 Vac
0.25 A at 250 Vdc
0.50 A at 125 Vdc
when the Bell Alarm with Lockout reset button is firmly
pressed.
11
—
Figure 13. Bell Alarm with Lockout module.
The 600 V version is not UL listed.
—
Figure 14. Bell Alarm with Lockout connections on the right terminal block. The
contacts are shown
in the reset state.
—
Table 10. Bell Alarm with Lockout catalog numbers.
Operatio
n
The Bell Alarm with Lockout prevents reclosing of the switch
after a ground fault trip until the reset button on the front of
the module is pressed. This trip can be caused by a ground
fault condition detected by the Control Unit.
In addition, the Bell Alarm with Lockout provides normally
open (NO) and normally closed (NC) alarm outputs available
at the terminal block on the right side of the switch, as
illustrated in Figure 14. These outputs are returned to their
normal state