ABB | E-kit
12 | © 2022 ABB | - 1SDH002203A1002
RS-485 serial communication interface (COM1 port)
The next diagram illustrates an RS-485 network with Master device at the end of the serial line.
1. E-kit Master at the end of the bus line, pull-ups and pull-downs activated, bus termination with 120
Ω
resistors
2. Slave in the serial line.
3. Slave at the end of the serial line, termination with 120
Ω
resistors
There is no need for a termination resistor if the Master device is in the serial line. However, the pull-up and
pull-down resistors must be activated (see next diagram).
1. Slave at end of serial line, termination with 120
Ω
resistors
2. E-kit Master at end of serial line, pull-ups and pull-downs activated
3. Slave in the serial line
4. Slave at the end of the serial line, termination with 120
Ω
resistors
The following photo illustrates the COM1 terminal box of E-kit when it is inside the serial line.
Summary of Contents for PM5630
Page 1: ...DOC N 1SDH002203A1002 E kit User Manual ...
Page 2: ...ABB E kit 2 2022 ABB 1SDH002203A1002 ...
Page 4: ...ABB E kit 4 2022 ABB 1SDH002203A1002 ...
Page 31: ...31 2022 ABB 1SDH002203A1002 ABB E kit Technical specifications ...
Page 32: ...ABB E kit 32 2022 ABB 1SDH002203A1002 Technical specifications ...
Page 33: ... 1SDH002203A1002 ...