ABB PCS100 ESS User Manual Download Page 8

2 Model Definition

PCS100 ESS User Manual   |   2UCD190000E001 rev. J

8

2  Model Definition

2.1  Type Code

The PCS100 ESS type code is given in the product ta-
bles. The type code is a unique code for the specific
PCS100 ESS model and specifies all the components
that are used to construct the model. To the type code
given in the product tables options can be added,
which are called plus (+) codes.

The diagram on the right outlines the structure of the
type code:

 

            PCS100  19 - 14D - B21+…

Product Series
PCS100 ESS Code
Number of Modules
Type of Module
Mechanical Construction
Options

 

Number of Power Modules

This is the number of modules used in the PCS100 ESS system, which depends on the load kVA.
One PCS100 ESS cabinet can have up to 6 PCS100 power modules and one PCS100 ESS rack converter up to 32 mod-
ules. In case a bigger system is required multiple PCS100 ESS can be connected in parallel. In this case, the units must be
tied together with separate transformers or multi-winding transformers.

 

Type of Power Module

There are two types of power modules available for the PCS100 ESS, which differ in their DC voltage range. The D-type
module is suitable for DC voltages up to 820 Vdc. For higher DC voltages the C-type module has to be used, which can run
up to 1120 Vdc.

Parameters

D-Type Module

C-Type Module

Rated DC voltage

1

750Vdc (250 – 820 Vdc)

1000Vdc (250 – 1120 Vdc)

Rated AC voltage

2

480 Vac (150 – 480 Vac)

480 Vac (150 – 480 Vac)

Current at rated AC voltage

150 Aac

105 Aac

Nominal frequency

50/60 Hz

50/60 Hz

DC side grounding

DC side RFI grounded

DC side RFI grounded

AC side grounding

Floating (AC transformer coupled)

Floating (AC transformer coupled)

Note:

1

 Power derating is required for continuous operation above 780 Vdc and 1065 Vdc as illustrated in Figure 2-1.

2

 This is the standard rated AC voltage. Other operating voltages (as indicated in brackets) can be achieved based

  on sizing criteria and software settings. The product will be delivered set up for the voltage specified in the sizing
  tool.

Figure 2-1: Derating curve for continuous operation at high DC voltages

Load

Vdc

100%

80%

D-820V

C-1100V

D-780V

C-1065V

Summary of Contents for PCS100 ESS

Page 1: ...of applications With this optimized use of the energy stor age system the PCS100 ESS helps to deliver exceptional returns on investment The PCS100 ESS allows control of both real power P and reactive power Q enabling it to cover a wide range of system requirements Moreover advanced control features in the Virtual Gener ator mode of operation allow this storage system to em ulate generator behavior...

Page 2: ...d unrivalled service and sup port The quality accuracy and performance of the Company s products result from over 100 years of experience com bined with a continuous program of innovative design and development to incorporate the latest technology Quality Control The products listed in this catalogue are manufactured in an ISO 9001 accredited facility Registration No 2469 For more information Furt...

Page 3: ...em operating and adjusting the PCS100 ESS commissioning the PCS100 ESS Who should read this manual This manual is intended for integrators of the PCS100 ESS installation personnel operators Prerequisites An installation repair operator person working with the PCS100 ESS must be trained by ABB and have electrical operational and safety knowledge have sufficient training to operate in an accidentall...

Page 4: ...ator must not open doors or panels marked as containing hazardous voltages Many parts in this prod uct including printed circuit boards operate at lethal voltages DO NOT TOUCH components or connections that have voltage present DANGER Stored Charge Stored charge is present after the device is switched off DANGER Arc Flash Shorted terminals can cause arc flash resulting in severe burns severe eye i...

Page 5: ...ption and Setup 40 6 1 How it Works 40 6 2 Virtual Generator Mode VSI 40 6 3 Current Source Inverter Mode CSI 41 6 4 Selecting the System Mode VSI or CSI 41 6 5 Control Setup in Virtual Generator Mode 42 6 5 1 Fixed Power Mode and V F mode 43 6 5 2 Frequency and Voltage Droop 43 6 5 3 Generator Settings 43 6 6 Control Setup in CSI Mode 44 6 7 Inputs and Measurements 45 6 7 1 Source Selection for I...

Page 6: ...ters Error Codes 130 MODBUS TCP Supported Functions 130 MODBUS RTU RS 485 Supported Functions 130 General Status and Measurements Registers 131 Configuration Parameters 136 Control Parameters 139 Setpoint Status 141 CAN IO Board Status 142 Power Module Internal Temperatures 144 Rack Module Internal Temperatures 146 Frequency and Voltage Envelopes Parameters 147 Grouped Parameters 148 Modbus Error ...

Page 7: ...down according to anti islanding standards or to operate in is land mode where the PCS100 ESS operates disconnected from the main grid but continues to supply local loads When operating in island mode the PCS100 ESS can automatically re synchronize the islanded network with the main grid allow ing a seamless transfer back to grid connect mode 1 1 User Benefits Supports power system load levelling ...

Page 8: ...s or multi winding transformers Type of Power Module There are two types of power modules available for the PCS100 ESS which differ in their DC voltage range The D type module is suitable for DC voltages up to 820 Vdc For higher DC voltages the C type module has to be used which can run up to 1120 Vdc Parameters D Type Module C Type Module Rated DC voltage1 750Vdc 250 820 Vdc 1000Vdc 250 1120 Vdc ...

Page 9: ...left up to 16 modules C Center fed 16 modules rack RH side 16 modules 25 2 D Center fed 16 modules rack LH side 16 modules 25 Overview modules and racks Cabinets Rack with D Type Modules Rack with C Type Modules A10 1 6 modules B1x 1 8 modules B2x 9 14 modules C2x 15 16 modules1 B3x 15 22 modules C3x 23 24 modules1 B4x 25 28 modules C4x 29 32 modules1 B1x 1 8 modules B2x 9 16 modules B3x 17 24 mod...

Page 10: ... configuration not specified in this document will be denoted with a C T000 Tx ready 1 and 2 modules cabinet only C Customized solution contact factory VR1 Remote synch input 480x3 480 V 3 wire 480x4 480 V 4 wire 110x4 110 V 4 wire 110x3 110 V 3 wire 2 2 Examples of PCS100 ESS Type Codes PCS100 19 01D A10 PCS100 19 06D A10 PCS100 19 01C A10 T000 PCS100 19 01C A10 PCS100 19 03D A10 ...

Page 11: ...100 19 16C B22 PCS100 19 24C B3C PCS100 19 22C B3D Further information about rack s components con nection can be found in the PCS100 ESS Wiring Di agram 2UCD190xxxE301 Any other configuration not specified in this docu ment will be a customized solution contact factory PCS100 19 32C B4C ...

Page 12: ...2x3 12 2200x2041x703 1220 1800 34 5 120 PCS100 19 12D B2x3 13 2200x2041x703 1300 1950 37 4 130 PCS100 19 13D B2x3 14 2200x2041x703 1370 2100 40 3 140 PCS100 19 14D B2x3 15 2200x 1041 2041 x703 1710 2250 43 1 150 PCS100 19 15D C5 2x3 16 2200x 1041 2041 x703 1780 2400 46 0 160 PCS100 19 16D C5 2x3 17 2200x 1041 2041 x703 1850 2550 48 9 170 PCS100 19 17D B3x4 18 2200x 1041 2041 x703 1920 2700 51 8 18...

Page 13: ...00 19 08C B1x3 9 2200x2041x703 1020 945 21 2 90 PCS100 19 09C B2x3 10 2200x2041x703 1080 1050 23 5 100 PCS100 19 10C B2x3 11 2200x2041x703 1150 1155 25 9 110 PCS100 19 11C B2x3 12 2200x2041x703 1220 1260 28 2 120 PCS100 19 12C B2x3 13 2200x2041x703 1300 1365 30 6 130 PCS100 19 13C B2x3 14 2200x2041x703 1370 1470 32 9 140 PCS100 19 14C B2x3 15 2200x2041x703 1440 1575 35 3 150 PCS100 19 15C B2x3 16 ...

Page 14: ...onds 120 for 600 seconds1 Note 1 From 75 preload refer to document 2UCD190000E013 PCS100 ESS Overload Circuit protection Circuit breaker or fuse not included Voltage harmonic compatibility IEC 61000 2 4 Class 2 Utility THDv 8 Note For THDv 8 please refer to factory For applications where THDv is above 10 lifetime of com ponents may be significantly affected please refer to factory Power module vol...

Page 15: ... achieve the EMC claimed performance at the ESS demarcation point For More information please refer to ABB document 2UCD190000E006 ESS Transformer Requirements Performance Aligned with IEEE 519 IEEE 1031 2000 Grid connection monitoring Aligned with IEEE 1547 Japanese Grid Code 3 5 Environmental Operating temperature range 0 C to 50 C Temperature derating Above 40 C derate at 2 load per C Operating...

Page 16: ...al power supplies are suitable for industrial use and that cables are dimensioned appro priately Attention should also be given to the grounding of the supplies The 0Vdc of the 26 5 Vdc supply must be tied to ground at one point and the 230 Vac fan supply should be configured as a TN hard grounded supply Furthermore it is not recommended to connect other loads to the 26 5 Vdc supply or to intercon...

Page 17: ...an one cabinet is needed for the application On the other hand if rack construction is selected the certain parts are shipped separately and will have to be assem bled into the rack system before the PCS100 ESS system can be used As shown in more detail in section Error Reference source not found the maximum number of modules varies between rack and cabinet systems A single cabinet can contain up ...

Page 18: ... the grid to the energy storage and vice versa As shown in Figure 4 2 the PCS100 modules include a sine filter and a RFI filter as part of the assembly mean ing the power electronics and filters are integrated into one module Thanks to this and the use of state of the art IGBT technology the PCS100 modules have minimum impact on power quality of the supply network harmonics and power factor They a...

Page 19: ...erred to as PCS100 Compact Master Module and does not contain an internal power supply Figure 4 4 shows a Compact Master Module Figure 4 4 PCS100 Compact Master Module Connections on the Master Module The PCS100 ESS includes several control and control power connections for local and remote control and moni toring of the system All terminals are located on the PCS100 Master Module and are suitable...

Page 20: ...3 Relay output 250 Vac 30 Vdc 1 A NO RUN Status Normally Open 4 Relay output 250 Vac 30 Vdc 1 A NC WARNING Status Normally Closed 5 Relay output 250 Vac 30 Vdc 1 A C WARNING Status Common 6 Relay output 250 Vac 30 Vdc 1 A NO WARNING Status Normally Open 7 Relay output 250 Vac 30 Vdc 1 A NC FAULT Status Normally Closed 8 Relay output 250 Vac 30 Vdc 1 A C FAULT Status Common 9 Relay output 250 Vac 3...

Reviews: