37 |
P a g e
OVR-15, 27 & 38 LV cabinet Instruction Manual
Sr.
No.
Protection
IEC61850
Identification
Setting range
available in
RER615
For OVR-15 Recloser
600/1A CT & 15.5kV System Voltage
For OVR-27 Recloser
600/1A CT & 27kV System Voltage
For OVR-38 Recloser
600/1A CT & 38kV System Voltage
Setting Range to be
used
(in Nominal Values)
Setting Range to be
used
(in Absolute Values)
Setting Range to be
used
(in Nominal Values)
Setting Range to be
used
(in Absolute Values)
Setting Range to be
used
(in Nominal Values)
Setting Range to be
used
(in Absolute Values)
EFHPTOC
0.05...15.00
0.05...15.00
30-9000A
0.05...15.00
30-9000A
0.05...15.00
30-9000A
Operate delay time
FEFLPTOC
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
EFHPTOC
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
EFIPTOC
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
4
Optional Directional earth-fault protection (FDEFxPDEF) main settings
Start Value
FDEFLPDEF
0.010...5.000 × In
0.010...5.000 × In
6-3000A
0.010...5.000 × In
6-3000A
0.010...5.000 × In
6-3000A
DEFHPDEF
0.10...40.00 × In
0.10...20.83 × In
60-12500A
0.10...20.83 × In
60-12500A
0.10...26.6 × In
60-16000A
Directional mode
FDEFLPDEF
and
DEFHPDEF
1 = Non-
directional
1 = Non-directional
1 = Non-
directional
1 = Non-
directional
1 = Non-
directional
1 = Non-
directional
1 = Non-
directional
2 = Forward
2 = Forward
2 = Forward
2 = Forward
2 = Forward
2 = Forward
2 = Forward
3 = Reverse
3 = Reverse
3 = Reverse
3 = Reverse
3 = Reverse
3 = Reverse
3 = Reverse
Time multiplier
FDEFLPDEF
0.05...15.00
0.05...15.00
0.05...15.00
0.05...15.00
0.05...15.00
0.05...15.00
0.05...15.00
DEFHPDEF
0.05...15.00
0.05...15.00
0.05...15.00
0.05...15.00
0.05...15.00
0.05...15.00
0.05...15.00
Operate delay time
FDEFLPDEF
60...200000 ms
60...200000 ms
60...200000 ms
60...200000 ms
60...200000 ms
60...200000 ms
60...200000 ms
DEFHPDEF
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
5
Transient/intermittent earth-fault protection (INTRPTEF) main settings
Directional mode
INTRPTEF
1=Non-directional 1=Non-directional
1=Non-directional 1=Non-directional 1=Non-directional 1=Non-directional 1=Non-directional
2=Forward
2=Forward
2=Forward
2=Forward
2=Forward
2=Forward
2=Forward
3=Reverse
3=Reverse
3=Reverse
3=Reverse
3=Reverse
3=Reverse
3=Reverse
Operate delay time
INTRPTEF
40...1200000 ms
40...1200000 ms
40...1200000 ms
40...1200000 ms
40...1200000 ms
40...1200000 ms
40...1200000 ms
Voltage start value (voltage start
value for transient EF)
INTRPTEF
0.01...0.50 × Un
0.01...0.50 × Un
155V-7750V
0.01...0.50 × Un
270V-13500V
0.01...0.50 × Un
380-16000V
Operation mode
INTRPTEF
1=Intermittent EF 1=Intermittent EF
1=Intermittent EF 1=Intermittent EF 1=Intermittent EF 1=Intermittent EF 1=Intermittent EF
INTRPTEF
2=Transient EF
2=Transient EF
2=Transient EF
2=Transient EF
2=Transient EF
2=Transient EF
2=Transient EF
Peak counter limit (Min
requirement for peak counter
before start in IEF mode)
INTRPTEF
2...20
2...20
2...20
2...20
2...20
2...20
2...20
Min operate current
INTRPTEF
0.01...1.00 × In
0.01...1.00 × In
6A-600A
0.01...1.00 × In
6A-600A
0.01...1.00 × In
6A-600A
6
Optional Admittance-based earth-fault protection (EFPADM) main settings
Voltage start value
EFPADM
0.01...5.00 × Un
0.01…1.00 × Un
155V-15500V
0.01…1.00 × Un
270V-27000V
0.01…1.00 × Un
380-38000V
Directional mode
EFPADM
1 = Non-
directional
1 = Non-directional
1 = Non-
directional
1 = Non-
directional
1 = Non-
directional
1 = Non-
directional
1 = Non-
directional
2 = Forward
2 = Forward
2 = Forward
2 = Forward
2 = Forward
2 = Forward
2 = Forward
3 = Reverse
3 = Reverse
3 = Reverse
3 = Reverse
3 = Reverse
3 = Reverse
3 = Reverse
Operation mode
EFPADM
1 = Yo
1 = Yo
1 = Yo
1 = Yo
1 = Yo
1 = Yo
1 = Yo