REG_DI4_CONTACT_TYPE
647
R/W
0 = NO
1 = NC
REG_DI5_CONTACT_TYPE
648
R/W
See REG_DI4_CONTACT_TYPE values
REG_DI6_CONTACT_TYPE
649
R/W
See REG_DI4_CONTACT_TYPE values
REG_DI7_CONTACT_TYPE
650
R/W
See REG_DI4_CONTACT_TYPE values
REG_DI8_CONTACT_TYPE
651
R/W
See REG_DI4_CONTACT_TYPE values
REG_DI9_CONTACT_TYPE
652
R/W
See REG_DI4_CONTACT_TYPE values
REG_DI10_CONTACT_TYPE
653
R/W
See REG_DI4_CONTACT_TYPE values
REG_DI11_CONTACT_TYPE
654
R/W
See REG_DI4_CONTACT_TYPE values
REG_DO6_FUNCTION
655
R/W
0 = No function
1 = Emergency/alarm
2 = Line I status
3 = Line II status
4 = Change-over switch alarm
5 = Manual mode
6 = Disconnect secondary loads
7 = Pre-transfer signal
8 = I Status
9 = O Status
10 = II Status
REG_DO7_FUNCTION
656
R/W
See REG_DO6_FUNCTION values
REG_DO8_FUNCTION
657
R/W
See REG_DO6_FUNCTION values
REG_DO9_FUNCTION
658
R/W
See REG_DO6_FUNCTION values
REG_DO10_FUNCTION
659
R/W
See REG_DO6_FUNCTION values
REG_DO12_FUNCTION
660
R/W
See REG_DO6_FUNCTION values
REG_DO6_CONTACT_TYPE
661
R/W
0 = NO
1 = NC
REG_DO7_CONTACT_TYPE
662
R/W
See REG_DO6_CONTACT_TYPE values
REG_DO8_CONTACT_TYPE
663
R/W
See REG_DO6_CONTACT_TYPE values
REG_DO9_CONTACT_TYPE
664
R/W
See REG_DO6_CONTACT_TYPE values
REG_DO10_CONTACT_TYPE
665
R/W
See REG_DO6_CONTACT_TYPE values
REG_DO12_CONTACT_TYPE
666
R/W
See REG_DO6_CONTACT_TYPE values
REG_VOLT_THRESHOLD_LN1_MIN
881
R/W
5...30 %
REG_VOLT_THRESHOLD_LN1_MAX
882
R/W
5...30 %
REG_VOLT_THRESHOLD_LN2_MIN
883
R/W
5...30 %
REG_VOLT_THRESHOLD_LN2_MAX
884
R/W
5...30 %
REG_VOLT_HYSTERESIS_LN1_MIN
885
R/W
4...29 %
REG_VOLT_HYSTERESIS_LN1_MAX
886
R/W
4...29 %
REG_VOLT_HYSTERESIS_LN2_MIN
887
R/W
4...29 %
REG_VOLT_HYSTERESIS_LN2_MAX
888
R/W
4...29 %
REG_FREQ_THRESHOLD_LN1_MIN
891
R/W
1...10 %
REG_FREQ_THRESHOLD_LN1_MAX
892
R/W
1...10 %
REG_FREQ_THRESHOLD_LN2_MIN
893
R/W
1...10 %
REG_FREQ_THRESHOLD_LN2_MAX
894
R/W
1...10 %
REG_FREQ_HYSTERESIS_LN1_MIN
895
R/W
8...98 (0.8 ... 9.8 %)
REG_FREQ_HYSTERESIS_LN1_MAX
896
R/W
8...98 (0.8 ... 9.8 %)
REG_FREQ_HYSTERESIS_LN2_MIN
897
R/W
8...98 (0.8 ... 9.8 %)
REG_FREQ_HYSTERESIS_LN2_MAX
898
R/W
8...98 (0.8 ... 9.8 %)