31
AUTOM ATIC CONTROL U N IT, OM D8 0 0
AU TO M AT I C CO N T R O L U N I T, O M D 8 0 0
Password Authentication
K
A00257
0
000
Back
Edit
Forward
System Configuration
Rated Voltage
Rated Frequency
Number of Phases LN1
1/13
K
A00258
System Configuration
Number of Phases LN2
Ext Voltage Transformer
Ext VT Primary Voltage
6/13
A0
71
24
7.2.2.3 System Configuration
In the System Configuration subpage user can configure parameters of the monitored lines; see Table
7.3. The parameter selection and its value changes are made by using UP, DOWN and ENTER keys.
The System Configuration subpage requires a password. Password consists of 4 numbers, it is given by
UP, DOWN and ENTER keys. The default password is 0001. Please, change the default password to your
own. The password is valid one minute after leaving the password protected subpage. If the password
is forgotten or lost, please, contact product support.
Figure 7.9
System Configuration requires a password
System Configuration
Ext VT Secondary Voltage
Secondary Load
Generator Usage
9/13
A0
71
29
System Configuration
Line Priority
Changeover Switch Type
Manual Back Switching
12/13
A0
7133
System Configuration
Changeover Switch Type
Manual Back Switching
Generator Shutdown
13/13
A0
7135
Table 7.3
Parameters and values of the System Configuration
Parameter
Values
Rated Voltage
100/57 V - 115/66 V - 120/70 V - 208/120 V - 220/127 V -
230/132 V -
240/138 V - 277/160 V - 347/200 V - 380/220 V - 400/230 V -
415/240 V - 440/254 V - 480/277 V
Rated Frequency
50 Hz and 60 Hz
Number of Phases LN1
3 phases with N / 3 phases without N / 1 phase
Number of Phases LN2
3 phases with N / 3 phases without N / 1 phase
Ext. Voltage Transformer
Absent / Present
Ext. VT Primary Voltage
100/57 V - 115/66 V - 120/70 V - 208/120 V - 220/127 V -
230/132 V -
240/138 V - 277/160 V - 347/200 V - 380/220 V - 400/230 V -
415/240 V -
440/254 V - 480/277 V - 500/288 V - 550/317 V - 600/347 V -
660/380 V - 690/400 V - 910/525 V - 950/550 V - 1000/577 V -
1150/660 V
Ext. VT Secondary Voltage
100/57 V - 115/66 V - 120/70 V - 208/120 V - 220/127 V -
230/132 V -
240/138 V - 277/160 V - 347/200 V - 380/220 V - 400/230 V -
415/240 V - 440/254 V - 480/277 V
Secondary Load
Not Used / Opening Only / Opening And Closing / Opening
Pulse /
Opening/Closing Pulse
Generator Usage
No Generator / Generator In Use
Line Priority
Line 1 – Switch I / Line 2 – Switch II / No Line Priority
Changeover Switch Type
Automatic OTM_C_D / Motorized OTM_C
Manual Back Switching
Off / On
Generator Shutdown
Off / On