background image

Technical data

Voltage and current limits

Rated AC voltage

220 … 240 V +/-20%, 50/60 Hz +/-10%

Output current

Max 4 A

Operating time

2 s

Main circuit connections

X11:1

Line I Phase

X11:2

Line I Neutral

X13:1

Line II Phase

X13:2

Line II Neutral

X12:1

Motor operator Phase

X12:2

Motor operator Neutral

Connection cables

Supply side cables of the main circuit

0,2 ... 2,5 mm

2

Load side cables of the main circuit

0,2 ... 2,5 mm

2

External transformer

When ODPS230 is used in network where N is not connected an external transformer must be used to drop voltage 

level. Transformer has to be Main to Phase transformer and isolative. Effective value depends on the size of the mo-

tor operator. See Connection diagram.

Dielectric properties

Overvoltage category

III

IEC 60947- 1 Rated impulse withstand voltage (Uimp), basic 

insulation  

4,0 kV

IEC 60947-1 Dielectric test

1,89 kV, 50 Hz, 5 s

IEC 60092-504 Insulation resistance measurement

> 100 M

, 500 V DC

Mechanical characteristics

Material of Enclosure

Self-extinguishing thermoplastic, UL 94 V-0

Degree of protection 

IP 20

Dimensions

Height

90 mm

Width

32 mm

Depth

130 mm

Environmental conditions

Ambient air temperature

-25 … +60 °C 

Altitude of the site of installation

< 2000 m

IEC 60068-2-30 Humidity, relative

< 93 %, T = -25 ... +60 °C

IEC 60947-1 Pollution degree

 3

Mechanical tests

IEC 60068-2-6 Vibration test

5 Hz to 13,2 Hz: +/-1 mm

13,2 Hz to 100 Hz: +/- 0,7 g

Q does not exceed 5

Duration 90 min at 30 Hz or at each resonance fre-

quency

IEC 60068-2-27 Shock test

Acceleration 100 m/s

 peak (10g

n

) and 150 m/s

2

 peak 

(15g

n

). Pulse duration: 11 ms

Transport and storage
Ambient air temperature

-40 … +70 °C

EMC characteristics
IEC 61000-4-2 Electrostatic discharge immunity test

8kV (Level 3) Air discharge

4kV (Level 2) Contact discharge

IEC 61000-4-3 Radiated, radio-frequency, electromagnetic 

field immunity test

Level 3

IEC 61000-4-4 Electrical fast transient/burst immunity test

Level 3

IEC 61000-4-5 Surge immunity test

2kV Phase to Neutral

IEC 61000-4-6 Immunity to conducted disturbances, induced 

by radio-frequency fields

Level 3

IEC 61000-4-8 Power frequency magnetic field immuntiy test Level 4
CISPR 11 Electromagnetic disturbance characteristics 

(Emission)

Group 1 Class B

Table 2 Technical data

Reviews: