19.0 Technical specification for NAL/NALF switch disconnectors NAL 12 – 17.5 – 24 – 36/6 – 12.5 A – K
Main functions
Item
Function
Mechanism type
Function limits
Reference control
12 kV
17.5/24 kV
36 kV
01
Closing speed of contact knifes
m/sec
5.5 – 5.8
6.5 – 6.8
4.7 – 6.3
Verified by manufacturer
02
Opening speed of contact knifes
m/sec
4.5 – 4.8
5.5 – 5.8
5 – 7
03
Maximum operating torque
Type K
Closing [Nm]
Opening [Nm]
70
90
100
Verified by manufacturer
80
100
120
Type A
Closing [Nm]
Opening [Nm]
90
110
120
5
5
5
04
Minimum distance between fixed contact
and contact knife of open switch
120 mm
212 mm
360 mm
Verified by manufacturer
05
Contact knife penetration
Both contact spots on each side
Control 100% by sight
06
Contact knife penetration
MUST make contact.
07
Contact knife alignment
Contact area = 26 mm
Tolerance of contact engagement 2-5 mm
(see fig. 16)
Control 100% by sight
The alignment is controlled by:
the main contact knife which must be
aligned with the main contact.
Control 100% by sight
The arcing knife runs straight and moves freely
in the arcing chamber, and makes full
engagement with the fixed arcing contact.
Must be adjusted
Item ref. 05 – 06 – 07