12 The configuration tool makes it possible to set the parameters in an easy way. Several MTQ22-FBP.0 devices can be created in the device tree (left).
The final configuration can be saved to the disk and downloaded into the devices using a standard USB cable.
Parameters
Master Configuration and Supervision
The MTQ22-FBP.0 supports up to four parallel connections to Modbus TCP clients (i.e. PLCs). It is possible to monitor these
clients for activity and signal a communication fault to the connected FBP devices after an adjustable timeout time.
For security reasons, the access to the MTQ22-FBP.0 can be limited to clients having IP addresses within a user defined
range. Single addresses or address ranges can be defined.
Network Settings
Before any Ethernet communication takes place, the MTQ22-FBP.0 must have an IP address. It is possible to provide a static
address or obtain the address via DHCP or the BootP protocol.
In the case of a static IP address, the netmask and the gateway address must also be set manually.
Device Settings
Up to four FBP devices can be connected to the MTQ22-FBP.0. For each port, the connected device type (or NONE) must be
specified. The MTQ22-FBP.0 then monitors the presence of the configured FBP device.
Position Supervision
The MTQ22-FBP.0 detects accidental permutation of devices connected to it. Therefore, a specific address (1...254) has to be
set per port which must match the address (1...254) set in the connected device. The MTQ22-FBP.0 offers status registers to
read the actual FBP device supervision status via Modbus TCP.
See the Address Map section for details.
Parameter Overview
Before using the MTQ22-FBP.0 device, the following parameters must be set:
Parameter name
Default settings
DHCP / BOOTP
Manual
IP Address
192.168.171.254
Subnet Mask
255.255.255.0
Standard Gateway
192.168.171.1
Number of Modbus TCP masters under supervision
1
Allowed number of supervised connections missing
0
Allowed Modbus TCP IP Address for master 1 ... 4
0.0.0.0 ... 255.255.255.255 for master 1
0.0.0.0 ... 0.0.0.0 for master 2-4
Timeout for master 1 ... 4
10s
Device port 1 ... 4 used
UMC100
Device address for device 1 ... 4
1,2,3,4