MegaFlex 1000 to 1600
UPS User Manual / REV-A
5. Insert the Inverter performing the “Inverter ON” command on first unit.
Perform the “Inverter ON” command from the screen:
Commands 1 / INVERTER /
ON
.
•
Soft-start of the Inverter indicated with blinking LED 2 (Inverter).
•
At the end of Inverter Soft-start the LED 2 (Inverter) remains lit.
•
In case of sufficient output power, the output will transfer to Inverter.
•
LED ALARM turns OFF and the LED LOAD PROTECTED must be lit.
Synoptic Diagram of first unit
Synoptic Diagram of other units
6. Insert the Inverter performing the “Inverter ON” command
on all other units.
Do not start the next Inverter until the sequence of the previous ends.
Perform the “Inverter ON” command from the screen:
Commands 1 / INVERTER /
ON
.
•
Soft-start of the Inverter indicated with blinking LED 2 (Inverter).
•
At the end of Inverter Soft-start the LED 2 (Inverter) remains lit.
•
As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with
running Inverter will transfer to Inverter.
•
LED ALARM turns OFF and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram, on all UPS units, must display the status “
Load supplied by Inverter
”.
Synoptic Diagram of first unit
Synoptic Diagram of other units
7. Operation mode selection.
MegaFlex 1000 to 1600 is delivered normally selected for permanent VFI operation.
If available, the eBoost™ Operation Mode (option) can be enabled and the eBoost Start Time & eBoost Stop
Time can be programmed for each day of the week (see Section 6.4 SETUP / eBoost).
End of Procedure
Note!
The Battery must be charged for at least 10 hours, in order to ensure the full backup runtime in case
of a Utility Failure.